Helios Rectifier 25/48

NT5C06D Installation and User Manual

6. Troubleshooting

Alarm indication

RFA fault

Table 9 - System fault diagnosis

Fault symptom

Possible causes

No AC input or input out of bounds.
No AC input or input out of bounds.
AC Input/DC output circuit breaker is open.
Rectifier has received a HVSD signal from the

controller.

An internal high voltage shutdown (HVSD) has

occurred. The internal High voltage shutdown point set too
low (below float or equalize setting).

Excessive impedance in one or both sense leads.
The cooling fan is failed.
DC circuit breaker is open.
A thermal shutdown has occurred.
Defective unit.
Excessive ambient air temperature.

RFA

Air inlet/outlet blocked, clogged air filter.