Installation and start-up 23

Helios Rectifier 25/48 Installation and User Manual

Table 4 - DC cable wire size

1 RECT. POSITION

2 RECT. POSITIONS

3 RECT. POSITIONS

8 AWG

6 AWG

4 AWG

Figure 6 - Connecting the DC power shelf

Control and Alarm Connections

The rectifier is interfaced to the power plant controller through the signal

connectors provided on the backplane of the power shelf (see Figures 1 and
2 for location). These signal connectors provide control, alarm, and

monitoring signals.

The power shelf provides two types of signal connectors. One ribbon cable

26-pin female connector, or multiple eight-pin male cable connectors are
used to interface the rectifiers to the power plant controller and monitoring

unit. The control inputs are activated by a BAT RTN signal. The alarm
signals extended by relay contacts are isolated from each other and from the

chassis. All contacts are rated 60 V DC and 0.5 A.