26 Installation and start-up

UM5C06D ( 169-2071-504 ) P0831010 Standard 7.00 May 2001

Figure 7 - No controller, remote sensing connection for 8-pin signal cable shelves

Note 1:

Refer to MS5C06 for available 8-pin ribbon signal cables

of different lengths to connect from the shelf back plane
rectifier position to the remote sensing point.

Note 2:

Identify the wire color corresponding to RG+ pin 2 and
RC- pin 3 to be used for the remote sensing. Completely

cut out completely the 8-pin connector, leaving the signal
wires loose. Insulate each unused wire with electrical tape.

Use the pin references to identify the signals as described
above.

Note 3:

Use #20 AWG (105°C) wire.

Note 4:

Use 1.6A fuse A0384386 with ferrule type fuse holder

A0384387.