beautypg.com

3 mimic display, 4 event controls, 5 event display – Emerson Liebert Static Transfer Switch User Manual

Page 96: 6 menu bar, 1 configuration menu, System ratings, Event masks, Mimic display, Event controls, Event display

background image

Liebert STS2 Touch Screen Display

88

13.3 Mimic Display

The Mimic display provides a color diagram of the operation of the Liebert STS2. This display imi-

tates the power flow through the static transfer switch and indicates source status, breaker status,

switch status, source voltage and current readings, output power measurements, and active alarm

messages. See Figure 48 on page 85.

13.4 Event Controls

The Liebert STS2 detects events when certain thresholds are passed or certain problems occur. The

alarm controls allow you to acknowledge the existence of these events.

• RESET — All latched events whose conditions have cleared are removed from the Event Display.

Faults and alarms that remain active, or are not recoverable, are not affected when this button is

selected. This button is also used to perform manual I-Peak resets and manual retransfers.

• SILENCE — turns off the audible alarm (horn or beeper) without resetting the triggering event.

This setting does not permanently turn off the horn. The alarm sounds again when the next event

with an audible alarm setting is triggered.

Active events are shown in the Event Display, whereas cleared events can be reviewed via the Event

Log.

13.5 Event Display

The Event Display lists the condition of the Liebert STS2 in real-time. Both nominal system parame-

ters and alarm messages are displayed in the Event Display. You can touch any message in the Event

Display to display more information in the Display Panel to the left. The selected status is displayed

in bold type.

13.6 Menu bar

As previously mentioned, the menu bar provides both configuration choices and information. The

choices under the Config and Log menus access additional dialog boxes, while the other menu choices

only show information in the display panel.

13.6.1 Configuration Menu

When you select the CONFIG (Configuration) menu choice, a pop-up menu is dis-

played with four choices.
System Ratingsused to configure frequency, voltage and currents settings for

the Liebert STS2.
Event Maskallows you to configure system’s response for events.
User Settingsallows you to configure operations for the Liebert STS2.
System Settingsaccesses another pop-up menu to configure communication and

system choices and the system ID.
Each of these choices accesses a separate dialog box.

System Ratings

The System Ratings menu is used to set the nominal line frequency, nominal voltage and nominal

current at which the system operates when it is installed. These settings are configured when the sys-

tem is initialized at the factory or under maintenance and should not be changed by the user.

Event Masks

The Liebert STS2 gathers, processes and reports faults and alarms, collectively referred to below as

events. The Event Mask dialog box allows you to set the system’s response for specific alarms and

faults that are generated. See 11.0 - Alarm and Faults for more information on events and 11.1 -

Event Mask for the definitions of the Event Mask types.