beautypg.com

Figures 11, System seismic anchoring, figure 1, Front – Emerson Liebert Static Transfer Switch User Manual

Page 32

background image

Installation Drawings

24

Figure 11 Seismic anchor drawing: 100 – 250 amp Liebert STS2

PS211105

Rev. 0

5. MOVE CABINET INTO POSITION WITH REAR TABS INTO SLOTS OF

FLOOR BRACKET. TABS TO EXTEND AT LEAST 1/2" THROUGH FLOOR

BRACKET (FIG. 2). THEN ATTACH FRONT FLOOR BRACKETS TO FRONT

CABINET BASE BRACKET BUT DO NOT FULLY

TIGHTEN HARDWARE.

6.

MARK

HOLE LOCATIONS AND REMOVE BRACKETS. DRILL AND INSTALL

FLOOR

BRACKETS. UNIT DOOR CAN BE REMOVED FOR BETTER ACCESS.

REINSTALL FRONT FLOOR BRACKETS TO FRONT CABINET BRACKETS WITH

SUPPLIED HARDWARE AND TORQUE TO 235 LB-IN (26.5 Nm), (FIG. 3).

7. IF SIDE WALLS ARE PRESENT, 5.0 INCH MINIMUM DISTANCE FROM EITHER

SIDE WALL IS REQUIRED.

8. REAR AND FRONT FLOOR BRACKETS, AND REAR AND FRONT CABINET

BASE BRACKETS ARE 1010 STEEL AND APPROX. .25 INCH THICK.

NOTES:

1. RECOMMENDED FLOOR ANCHOR: 1/2" ITW RAMSET/RED HEAD

SELF DRILLING ANCHOR, ICBO #ER-1372 OR EQUIVALENT (NOT

(SUPPLIED). FOLLOW MANUFACTURER'S INSTRUCTIONS.

2. POSITION REAR FLOOR BRACKETS ON FLOOR AT LEAST .75"

FROM

BACK WALL. MARK LOCATION AND DRILL HOLES (FIG. 1) TO

A MINIMUM DEPTH OF 4.12" INTO THE CONCRETE.

3. INSTALL REAR CABINET BASE BRACKET (FIG. 2) TO EXISTING

HOLES ON UNDERSIDE OF UNIT WITH TABS FACING BACK WALL.

USE SUPPLIED HARDWARE AND TORQUE TO 365 LB-INCH (41.2 Nm).

NOTE, LOOSEN LEVELING BOLT LOCKING NUT AND TIGHTEN AFTER

BRACKET IS SECURED.

4. INSTALL FRONT CABINET BASE BRACKET (FIG. 3) TO EXISTING

HOLES

ON

UNDERSIDE

OF

UNIT WITH BENT FLANGE FACING FRONT.

USE SUPPLIED HARDWARE AND TORQUE TO 365 LB-INCH (41.2 Nm).

NOTE, LOOSEN LEVELING BOLT LOCKING NUT AND TIGHTEN AFTER

BRACKET IS SECURED.

SYSTEM SEISMIC ANCHORING, FIGURE 1

FLOOR LINE

FLOOR LINE

FRONT CABINET

BASE BRACKET

HARDWARE

SUPPLIED

FRONT DOOR

TOP VIEW

FIGURE 3

FIGURE 2

REAR FLOOR

BRACKET

FLOOR ANCHOR

HARDWARE

(NOT SUPPLIED)

REAR CABINET

BASE BRACKET

BACK

WALL

APPROX 1/2"

FRONT FLOOR

BRACKET

OF CABINET

FLOOR ANCHOR

HARDWARE

NOT SUPPLIED

(335 M

M

)

(107

M

M

)

4.

2"

(335 M

M

)

13

.2

"

13

.2

"

32.

75

"

(8

32 M

M

)

(107

M

M

)

(256 M

M

)

FRONT

10

.1"

4.

2"

(146 M

M

)

5.

7

5"

BACK WALL

REAR FLOOR

BRACKET

SEE NOTE (2)

FOR SPACING

SIDE WALL

FRONT FLOOR

BRACKET

SEE NOTE (7)

FOR SPACING