Alarm and Faults
74
.
Table 8
Event messages
ID
Alarm Message
Description/Cause
Action
001
S1 SCR SHORT
One or more of the SCRs for Source 1 have shorted and failed.
D, F, A, E
002
S2 SCR SHORT
One or more of the SCRs for Source 2 have shorted and failed.
D, F, A, E
003
S1 SCR OPEN
One or more of the SCRs for Source 1 is open.
D, F, A, E
004
S2 SCR OPEN
One or more of the SCRs for Source 2 is open.
D, F, A, E
005
PRIMARY FAN FAIL
A primary cooling fan has failed and the unit is now being
cooled by a secondary fan, which is not monitored.
D, A, E
006
CONTROL MODULE FAIL
Control logic module has failed.
D, A, E
007
PWR SPLY DC A FAIL
Power supply DC bus A has failed.
D, A, E
008
PWR SPLY DC B FAIL
Power supply DC bus B has failed.
D, A, E
009
PWR SPLY S1 AC FAIL
Power supply Source 1 AC has failed.
D, A, E
010
PWR SPLY S2 AC FAIL
Power supply Source 2 AC has failed.
D, A, E
011
PWR SPLY LOGIC FAIL
A power supply module has failed.
D, A, E
012
OUT VOLT SENSE FAIL
The output volt sense module failed
D, A, E
013
S1 VOLT SENSE FAIL
The Source 1 volt sense module failed.
D, A, E
014
S2 VOLT SENSE FAIL
The Source 2 volt sense module failed.
D, A, E
015
S1 SCR SENSE FAIL
The Source 1 SCR sense module failed.
D, A, E
016
S2 SCR SENSE FAIL
The Source 2 SCR sense module failed.
D, A, E
017
S1 CURR SENSE FAIL
The Source 1 SCR current module failed.
D, A, E
018
S2 CURR SENSE FAIL
The Source 2 SCR current module failed.
D, A, E
019
S1 GATE DRIVE FAIL
The Source 1 gate drive module failed.
D, A, E
020
S2 GATE DRIVE FAIL
The Source 2 gate drive module failed.
D, A, E
021
INTERNAL COMM FAIL
Internal CAN communications failed.
D, A, E
022
EXTERNAL COMM FAIL
Options CAN communications failed.
A, E
023
CB1 SHUNT TRIP FAIL
CB1 shunt trip failed.
A, E
024
CB2 SHUNT TRIP FAIL
CB2 shunt trip failed.
D, A, E
064
HEATSINK OVERTEMP
Heatsink has exceeded the recommended temperature.
A, E
067
S1 UV
Source 1 under voltage, fast detection.
A, E
068
S1 UV (RMS)
Source 1 under voltage, slow detection.
L, A, E
069
S1 OV
Source 1 over voltage
A, E
070
S1 OF/UF
Source 1 over frequency/under frequency
A, E
071
S1 FAIL
Source 1 failure.
A, E
072
S2 UV
Source 2 under voltage, fast detection.
A, E
073
S2 UV (RMS)
Source 2 under voltage, slow detection.
A, E
074
S2 OV
Source 2 over voltage.
A, E
075
S2 OF/UF
Source 2 over frequency/under frequency.
A, E
076
S2 FAIL
Source 2 failure.
A, E
077
S1 OVERCURRENT
Source 1 over current.
A, E
078
S2 OVERCURRENT
Source 2 over current.
A, E
079
S1 I-PEAK
I-PK on Source 1.
A, F, E
080
S2 I-PEAK
I-PK on Source 2.
A, F, E
081
SOURCES OUT OF SYNC
Source 1 and Source 2 are out of synchronization.
A, E
082
LOAD ON ALT SOURCE
The output load is running on the alternate source.
A, E
083
AUTO REXFER INHIBIT
Automatic retransfer is inhibited.
A, E