beautypg.com

4 normal system shutdown, Shutdown in static transfer switch mode, Shutdown in maintenance bypass mode – Emerson Liebert Static Transfer Switch User Manual

Page 118

background image

Operating the Liebert STS2 LED Display

110

14.2.4 Normal System Shutdown

The Liebert STS2 can be shut down from either the static switch mode or the bypass mode.

Shutdown in Static Transfer Switch Mode

When the Static Transfer Switch is operating on static transfer switch mode (not mainte-

nance bypass mode):
1. Turn off the load equipment per manufacturer’s recommendations.
2. Open CB3 to turn off the static switch output.

• Open CB3A if the static transfer switch is a redundant output configuration.

The LEDs for CB3 and CB3A (if supplied) and the output (OUT) are turned off.

3. Open the input switches CB1 and CB2.

The LEDs for CB1 and CB2 are turned off.

4. To completely de-energize the unit, turn OFF the power to both inputs to the Liebert STS2.

Shutdown in Maintenance Bypass Mode

When the Static Transfer Switch is operating on bypass:
1. Turn off the load equipment per manufacturer’s recommendations.
2. Open the bypass switch (CB4 or CB5) to turn off the static transfer switch output.

The LED for the bypass switch is turned off.
The output (OUT) LED is turned off.

3. To completely de-energize the unit, turn OFF the power to both inputs to the Liebert STS2.