beautypg.com

0 specifications, 1 system configuration, 1 frequency – Emerson Liebert Static Transfer Switch User Manual

Page 119: 2 input/output voltage, Table 16 input/output voltage, 3 system current ratings, Table 17 system current ratings, Pecifications, System configuration, Table 16

background image

Specifications

111

15.0 S

PECIFICATIONS

This section provides the specifications for the Liebert STS2.

15.1 System Configuration

The Liebert STS2 can be set in several different configurations, according to the model and location.

The configuration is set at the factory and does not need to be changed by the customer. These config-

urations apply to both units, the Color Graphical Display and an LED Display.

15.1.1 Frequency

The Liebert STS2 accepts input frequencies of 50 Hz and 60 Hz. The frequency shall be within

± 0.5Hz of the nominal frequency.

15.1.2 Input/Output Voltage

The Liebert STS2 models are available to handle various voltages.
The input voltage must be three-phase AC (3 or 4 wire-plus-ground). The Liebert STS2 is designed to

accept an input neutral from each source. The neutral is switched in the 4-pole static transfer switch

only.
The voltage shall be within ± 10% of the nominal voltage.
The output voltage shall be three-phase AC (3 or 4 wire-plus-ground). Nominal output voltage shall

be same as input voltage.
The following table provides nominal voltages, listed according to frequency.

15.1.3 System Current Ratings

These ratings are based upon continuous switch current rating. These ratings are for all voltages and

frequencies. All units are 100% continuous current rated.

Table 16

Input/output voltage

60Hz

50 Hz

[L-L/L-N]

[L-L/L-N]

200/115V

200/115V

208/120V

208/120V

220/127V

220/127V

240/139V

240/139V

380/220V

380/220V

400/230V

400/230V

415/240V

415/240V

480/277V
600/346V

Table 17

System current ratings

Current

100
250
400
600
800

1000