Figure 58 programmable relay board dialog box – Emerson Liebert Static Transfer Switch User Manual
Page 106
Liebert STS2 Touch Screen Display
98
Figure 58 Programmable relay board dialog box
2. Select your configuration settings.
• Select STANDARD SET to use the settings configured at the factory. See Go to step 4.
• Select USER DEFINED SET to configure your own settings. Go to step 3.
If you enter a user-defined setting, record the setting in Programmable Relay Board Settings
Record on page 140. If for some reason the control board is replaced, it will be necessary to
reprogram the Programmable Relay Board with this information.
3. To define your relay board settings:
a. Select a Programming Relay.
b. Select an event you want associated with the relay. That fault is placed in the Relay column.
You can associate up to ten (10) events with one relay. If you do so, you should group the
events logically to simplify troubleshooting when an event is triggered.
4. Select SAVE to keep the settings.
5. Select OK for the applicable Programmable Options Board option in the Comm Options dialog box
to activate the settings.
Configuring the Liebert IntelliSlot Web/485 Card With Adapter
An optional Liebert IntelliSlot Web/485 Card With Adapter (IS-WEB485ADPT) can be installed in
the Liebert STS2 to provide Ethernet connectivity via an RJ-45 port.
Ethernet cabling is the responsibility of the customer. Category 5 cabling is required.
See 6.6 - Liebert IntelliSlot
Web/485 Card With Adapter for more information on the Liebert
IS-WEB485ADPT. See the card’s user guide, SL-52615, for configuration instructions. The guide is
available at Liebert’s Web site
If the optional Liebert IS-WEB485ADPT is installed in the Liebert STS2:
• Select YES for the Liebert IS-WEB485ADPT option in the Comm Options dialog box to activate
the card.