Emerson Liebert Static Transfer Switch User Manual
Page 88

Communication Interfaces
80
Group 3:
User
Settings
1
SCR1 Fast Undervoltage
Setpoint
Integer
In % of nominal below nominal
2
SCR1 Slow Undervoltage
Setpoint
Integer
In % of nominal below nominal
3
SCR1 Slow Undervoltage
Detect Delay
Integer
In number of lines cycles
4
SCR1 Overvoltage
Setpoint
Integer
In % of nominal above nominal
5
SCR1 Overvoltage Detect
Delay
Integer
In 1/4 lines cycles
6
SCR1 I peak Transfer
Setpoint
Integer
x 10
7
SCR2 Fast Undervoltage
Setpoint
Integer
In % of nominal below nominal
8
SCR2 Slow Undervoltage
Setpoint
Integer
In % of nominal below nominal
9
SCR2 Slow Undervoltage
Detect Delay
Integer
In number of lines cycles
10
SCR2 Overvoltage
Setpoint
Integer
In % of nominal above nominal
11
SCR2 Overvoltage Detect
Delay
Integer
In 1/4 lines cycles
12
SCR2 I peak Transfer
Setpoint
Integer
x 10
13
Max. Transfer Phase
Angle
Integer
In degrees
14
Output Frequency
Deviation
Integer
Freq. in Hz x 10
15
ReTransfer Delay Time
Integer
In seconds
16
Horn Volume
Integer
Range: 1-10
17
Critical Option Enabling
Bitpacked
18
Non-Critical Option
Enabling
Bitpacked
Group 4:
Event Mask
Settings
1 to
63
Event Mask settings for
faults
Event Mask
See section 12.1.4.
64 to
143
Event Mask settings for
alarms
Event Mask
See section 12.1.4.
Table 11
Group settings and values (continued)
Group
Item:
Description
Value Type
Value Notes