Figure 26 control wiring for comms board, Figure 26 fo – Emerson Liebert Static Transfer Switch User Manual

Page 47

background image

Installation Drawings

39

Figure 26 Control wiring for comms board

EXTERNAL MODEM

SEE DETAIL A

“NO CUSTOMER

CONNECTION”

PS213003
Rev. 02

LIEBERT

SITESCAN

SEE DETAIL B

“NO CUSTOMER

CONNECTION”

J81

J1A

COMMS BOARD

02-810015-XX

TB55

TB56

TB51

SEE NOTE 2

CUSTOMER-SUPPLIED

INTERCONNECTING CABLE

TO EXTERNAL MODEM

CUSTOMER-SUPPLIED

INTERCONNECTING CABLE

TO LIEBERT SITESCAN

SEE NOTES 1 & 2

DETAIL A

9

1 2 3 4 5 6 7 8

J81

RI

DS

R

RX TX DT

R

GN

D

DC

D

RT

S

CT

S

DETAIL B

TB 55

1 2 3

NOTES

1. Maximum cable length 1000 feet (300 meters) with

twisted pair cable #22 AWG 300V minimum.

2. Signal voltage 5VDC, current 10mA.

3. Refer to installation, operation and maintenance

manual for configuring the COMMS board.

4. All control wiring (by others) must be run separate from

power wiring. Control wiring runs should not be

combined in the same conduit.

5. Refer to control connection location diagram of static

transfer switch for location of COMMS board.

6. All wiring must be in accordance with national and

local electrical codes.