beautypg.com

4 access, 5 circuit breakers, 6 cable entrance – Emerson Liebert Static Transfer Switch User Manual

Page 122: 7 doors, 8 color graphical display or led display, 5 - circuit breakers fo, Warning

background image

Specifications

114

15.2.4 Access

The Liebert STS2 is designed so all repairs and maintenance can be done from the front or top of the

unit. All components that may need repair or replacement during routine field maintenance are

safely accessed with the units in bypass without removing power from the unit. These components

include:

• All electronic PCB assemblies
• Power supply assemblies
• All fuses
• All circuit breaker plug-in modules
• Fans
• SCRs

All power connections are designed to maintain proper connection torque over the lifetime of the unit

without any maintenance. The integrity of the connections can be checked via infrared scanning

safely from the front or top of the unit.
All other components including power cables and connections, circuit breaker bases, etc. are replace-

able from the front or top of the unit only, but this requires all power to be removed from the unit for

safety. Although routine re-torquing of the power connections is not required, if maintenance of these

connections is needed, complete removal of power is required from the unit for safety reasons.

15.2.5 Circuit Breakers

The Liebert STS2 is equipped with five molded-case, plug-in, non-automatic circuit breakers. The

breakers are UL-listed for use up to 600 VAC and CE-marked. The plug-in feature of the breaker

includes an interlock, which prevents the breaker from being unplugged without being in the OFF

(open) position.
Mechanical interlocks are provided on the breakers to prevent improper maintenance bypassing of

the solid-state switch. A bypass breaker cannot be closed unless the solid-state switch is connected to

the same input source and only one bypass breaker can be closed at a time. All breakers are equipped

with N.O. and N.C. auxiliary switches for monitoring of the breaker positions. The two input breakers

for the solid-state switching devices also are equipped with 48 VDC shunt trips to allow for control by

the Liebert STS2 logic. See Figure 20 - Liebert STS2 non-automatic circuit breaker schedule.

15.2.6 Cable Entrance

Removable conduit termination plates are provided in the top and bottom of the Liebert STS2 for ter-

mination of the two source input conduits or raceways and/or the output conduits or raceways.

15.2.7 Doors

A removable key lock hinged front door provides access to the circuit breakers.

15.2.8 Color Graphical Display or LED Display

The display is located in the front of the unit. Front panel display is either an LCD touch screen dis-

play for monitoring and configuring the unit, or an LED panel to monitor the unit's status.
See Figure 30 for a drawing of the touch screen display. See Figure 62 for the layout of the LED dis-

play.

!

WARNING

Lethal voltages exist inside the unit during normal operation. Only qualified service

personnel should perform maintenance on the static switch.
The unit is supplied by more than one power source. The unit contains hazardous voltages if

any of the input sources is ON, even when the unit is in bypass. To isolate the unit, turn OFF

and lock out ALL input power sources.
Verify that all input power sources are de-energized and locked out before making connections

inside unit.