Yaskawa G7 Modbus Communication User Manual
Page 69

69
Table 4.11 “L” Parameters
Access Level
Name
Address
Description
Data
Range
Unit
Default
During
Run
V/f
V/f
w/PG
OLV
FV
OLV2
L5-01
049Eh
Number of Auto-Restarts
0 ~ 10
1
0
A
A
A
A
A
0
No Fault Relay
L5-02
049Fh
Fault Selection During
Auto-Restart
1
Fault Relay Active
1
0
A A A A A
0 Disabled
1
Overtorque, Speed Agree,
Alarm
2
Overtorque, Run, Alarm
3
Overtorque, Speed Agree,
Fault
4
Overtorque, Run, Fault
5
Undertorque, Speed Agree,
Alarm
6
Undertorque, Run, Alarm
7
Undertorque, Speed Agree,
Fault
L6-01
04A1h
Torque Detection 1
Selection
(OL3, UL3)
8
Undertorque, Run, Fault
1
0
A A A A A
L6-02
04A2h
Torque Detection 1
Level
0 ~ 300 %
1 %
150 %
A
A
A
A
A
L6-03
04A3h
Torque Detection 1 Time
0.0 ~ 10.0 Sec
0.1 Sec
0.1 Sec
A
A
A
A
A
0 Disabled
1
Overtorque, Speed Agree,
Alarm
2
Overtorque, Run, Alarm
3
Overtorque, Speed Agree,
Fault
4
Overtorque, Run, Fault
5
Undertorque, Speed Agree,
Alarm
6
Undertorque, Run, Alarm
7
Undertorque, Speed Agree,
Fault
L6-04
04A4h
Torque Detection 2
Selection
(OL4, UL4)
8
Undertorque, Run, Fault
1
0
A A A A A
L6-05
04A5h
Torque Detection 2
Level
0 ~ 300 %
1 %
150 %
A
A
A
A
A
L6-06
04A6h
Torque Detection 2 Time
0.0 ~ 10.0 Sec
0.1 Sec
0.1 Sec
A
A
A
A
A
L7-01
04A7h
Torque Limit Forward
Motoring
0 ~ 300 %
1 %
200 %
A
A
A
L7-02
04A8h
Torque Limit Reverse
Motoring
0 ~ 300 %
1 %
200 %
A
A
A
L7-03
04A9h
Torque Limit Forward
Regeneration
0 ~ 300 %
1 %
200 %
A
A
A
L7-04
04AAh
Torque Limit Reverse
Regeneration
0 ~ 300 %
1 %
200 %
A
A
A
L7-06
04ACh
Torque Limit Filter Time
5 ~ 10000 ms
1 ms
200 ms
A
0 P
Control
L7-07
04C9h
Torque Limit Control
Selection During
Accel/Decel
1 PI
Control
1
0 A
0 Not
Provided
L8-01
04ADh
Dynamic Braking
Resistor Protection
Selection
(Only for Yaskawa 3%
heatsink mounted
resistors)
1 Provided
1
0
A A A A A
L8-02
04AEh
Overheat (OH)
Pre-Alarm Level
50 ~ 130 Deg
1 Deg
95 Deg
A
A
A
A
A
0
Ramp to Stop
1
Coast to Stop
2 Fast-Stop
(C1-09)
L8-03
04AFh
Overheat (OH) Pre-
Alarm Selection
3 Alarm
Only
1
3
A A A A A
0 Disabled
L8-05
04B1h
Input Phase Loss (PF)
Selection
1 Enabled
1
0
A A A A A
0 Disabled
L8-07
04B3h
Output Phase (LF) Loss
Method Selection
1
1 Phase Loss Detection
1
0
A A A A A