Yaskawa G7 Modbus Communication User Manual
Page 67

67
Table 4.10 “H” Parameters
Access
Name
Address
Digital Operator Display
Text
Data
Range
Unit
Default During
Run
V/f
V/f
w/PG
OLV
FV
OLV2
32 ACR
(Iq)
Output
33 ACR
(Id)
Output
36 PID
Input
37 PID
Output
38 PID
Setpoint
42 Estimated
Motor
Flux
43
Id Compensation Value
44 ASR
Output
Without
Filter
45
Feed Forward Output
H4-01
041Dh
Analog Output Terminal FM
Function Selection
48
Stabilizing Speed at Regeneration
(OLV2)
1 02h - - - - -
H4-02
041Eh
Terminal FM Gain
0.0 ~ 1000.0 %
0.1 %
100.0 %
R Q Q Q Q Q
H4-03
041Fh
Terminal FM Bias
-110.0 ~ 110.0 %
0.1 %
0.0 %
R
A
A
A
A
A
H4-04
0420h
Terminal AM Selection
See H4-01
1
03h
A
A
A
A
A
H4-05
0421h
Terminal AM Gain
0.0 ~ 1000.0 %
0.1 %
50.0 %
R Q Q Q Q Q
H4-06
0422h
Terminal AM Bias
-110.0 ~ 110.0 %
0.1 %
0.0 %
R
A
A
A
A
A
0 0-10
VDC
1
-10 +10 VDC
H4-07
0423h
Terminal FM Signal Type
Selection
(Set Jumper CN15 Also)
2 4-20
mA
1
0
A A A A A
0 0-10
VDC
1
-10 +10 VDC
H4-08
0424h
Terminal AM Signal Type
Selection
(Set Jumper CN15 Also)
2 4-20
mA
1
0
A A A A A
H5-01
0425h
Terminals R+, R-, S+, S-
Modbus Node Address
0h
~
20h
1
1Fh A A A A A
0 1200
bps
1 2400
bps
2 4800
bps
3 9600
bps
H5-02
0426h Baud
Rate
4 19200
bps
1
3
A A A A A
0 No
Parity
1 Even
Parity
H5-03
0427h Parity
Selection
2 Odd
Parity
1
0
A A A A A
0
Ramp to Stop
1
Coast to Stop
2 Fast-Stop
(C1-09)
H5-04
0428h
Communication Loss Fault
(CE) Response Selection
3 Alarm
Only
1
3
A A A A A
0 Disabled
H5-05
0429h
Communication Loss Fault
(CE) Selection
1 Enabled
1
1
A A A A A
H5-06
042Ah
Transmit Wait Time
5 ~ 65 ms
1 ms
5 ms
A
A
A
A
A
0 Disabled
H5-07
042Bh RTS
Control
Selection
1 Enabled
1
1
A A A A A
0 0.1V
H5-10
0436h
Unit Selection for Modbus
Register 0025h (Output
Voltage Reference Monitor)
1 1V
1
0
A A A A A
0 Frequency
Reference
1 PID
Feedback
H6-01
042Ch
Pulse Input Terminal RP
Function Selection
2 PID
Setpoint
1
0
A A A A A
H6-02
042Dh
Pulse Input Scaling
1000 ~ 32000 Hz
1 Hz
1440 Hz
R A A A A A
H6-03
042Eh
Pulse Input Gain
0.0 ~ 1000.0 %
0.1 %
100.0 %
R A A A A A
H6-04
042Fh
Pulse Input Bias
-100.0 ~ 100.0 %
0.1 %
0.0 %
R
A
A
A
A
A
H6-05
0430h
Pulse Input Filter Time
0.00 ~ 2.00 Sec
0.01 Sec
0.1 Sec
R A A A A A
1 Frequency
Reference
2 Output
Frequency
20
Soft Starter (SFS) Output
24 PID
Feedback
31
Not Used (Set for Network Use)
H6-06
0431h
Pulse Output Terminal MP
Function Selection
36 PID
Input
1
02h R A A A A A
H6-07
0432h
Pulse Output Scaling
0 ~ 32000 Hz
1 Hz
1440 Hz
R A A A A A