Table 4.8 “E” Parameters
Access Level
Name
Address
Description
Data
Range
Unit
Default
During
Run
V/f
V/f
w/PG
OLV
FV
OLV2
E1-01
0300h
Input Voltage
0.0 ~ 255.0/510.0 VAC
1 VAC
kVA Dep.
Q Q Q Q Q
E1-04
0303h
Maximum Frequency
40.0 ~ 400.0 Hz
0.1 Hz
60.0 Hz
Q
Q
Q
Q
Q
E1-05
0304h
Maximum Voltage
0.0 ~ 255.0/510.0 VAC
0.1 VAC
kVA Dep.
Q Q Q Q Q
E1-06
0305h
Base Frequency
0.0 ~ 400.0 Hz
0.1 Hz
60.0 Hz
Q
Q
Q
Q
Q
E1-07
0306h
Midpoint Frequency A
0.0 ~ 400.0 Hz
0.1 Hz
Cntrl Meth
A A A
E1-08
0307h
Midpoint Voltage A
0.0 ~ 255.0/510.0 VAC
0.1 VAC
Cntrl Meth
A A A
E1-09
0308h
Minimum Frequency
0.0 ~ 400.0 Hz
0.1 Hz
Cntrl Meth
Q Q Q A Q
E1-10
0309h
Minimum Voltage
0.0 ~ 255.0/510.0 VAC
0.1 VAC
Cntrl Meth
A A A
E1-11
030Ah
Midpoint Frequency B
0.0 ~ 400.0 Hz
0.1 Hz
0.0 Hz
A
A
A
A
A
E1-12
030Bh
Midpoint Voltage B
0.0 ~ 255.0/510.0 VAC
0.1 VAC
0.0 VAC
A
A
A
A
A
E1-13
030Ch
Base Voltage
0.0 ~ 255.0/510.0 VAC
0.1 VAC
0.0 VAC
A
A
Q
Q
Q
E2-01
030Eh
Motor Rated FLA
kVA Dep.
0.01 A
kVA Dep.
Q Q Q Q Q
E2-02
030Fh
Motor Rated Slip
0.00 ~ 20.00 Hz
0.01 Hz
kVA Dep.
A A A A A
E2-03
0310h
No-Load Current
kVA Dep.
0.1 A
kVA Dep.
A A A A A
E2-04
0311h
Number of Poles
2 ~ 48
1
4
Q
Q
Q
E2-05
0312h
Terminal Resistance
0.000 ~ 65.000 Ohm
0.001 Ohm
kVA Dep.
A A A A A
E2-06
0313h
Leakage Inductance
0.0 ~ 40.0 %
0.1 %
kVA Dep.
A A A
E2-07
0314h
Saturation Compensation 1
0.00 ~ 0.50
0.01
0.50
A
A
A
E2-08
0315h
Saturation Compensation 2
0.00 ~ 0.75
0.01
0.75
A
A
A
E2-09
0316h
Mechanical Loss
0.0 ~ 10.0 %
0.1 %
0.0 %
A
A
A
E2-10
0317h
Motor Iron Loss
0 ~ 65535 W
1 W
kVA Dep.
A
A
E2-11
0318h
Motor Rated Power
0.00 ~ 650.00 kW
0.01 kW
kVA Dep.
Q Q Q Q Q
E2-12
0328h
Saturation Compensation 3
1.30 ~ 5.00
0.01
1.30
A
A
A
0 V/F
1 V/F
w/PG
2
Open Loop Vector
3 Flux
Vector
E3-01
0319h
Control Method
(Motor 2)
4
Open Loop Vector 2
1
2
A A A A A
E3-02
031Ah
Maximum Frequency (Motor 2)
40.0 ~ 400.0 Hz
0.1 Hz
60.0 Hz
A
A
A
A
A
E3-03
031Bh
Maximum Voltage (Motor 2)
0.0 ~ 255.0/510.0 VAC
0.1 VAC
230.0 VAC
A A A A A
E3-04
031Ch
Base Frequency (Motor 2)
0.0 ~ 400.0 Hz
0.1 Hz
60.0 Hz
A
A
A
A
A
E3-05
031Dh
Midpoint Frequency A (Motor 2)
0.0 ~ 400.0 Hz
0.1 Hz
Cntrl Meth
A A A
E3-06
031Eh
Midpoint Voltage A (Motor 2)
0.0 ~ 255.0/510.0 VAC
0.1 VAC
Cntrl Meth
A A A
E3-07
031Fh
Minimum Frequency (Motor 2)
0.0 ~ 400.0 Hz
0.1 Hz
Cntrl Meth
A A A A A
E3-08
0320h
Minimum Voltage (Motor 2)
0.0 ~ 255.0/510.0 VAC
0.1 VAC
Cntrl Meth
A A A
E4-01
0321h
Motor Rated FLA (Motor 2)
kVA Dep.
0.1 A
kVA Dep.
A A A A A
E4-02
0322h
Motor Rated Slip (Motor 2)
0.0 ~ 20.0 Hz
0.01 Hz
kVA Dep.
A A A A A
E4-03
0323h
No-Load Current (Motor 2)
kVA Dep.
0.01 A
kVA Dep.
A A A A A
E4-04
0324h
Number of Poles (Motor 2)
2 ~ 48
1
4
A
A
A
E4-05
0325h
Terminal Resistance (Motor 2)
0.000 ~ 65.000 Ohm
0.001 Ohm
kVA Dep.
A A A A A
E4-06
0327h
Leakage Inductance (Motor 2)
0.0 ~ 40.0 %
0.1 %
kVA Dep.
A A A A A
E4-07
0328h
Motor Rated Power (Motor 2)
0.00 ~ 650.00 kW
0.01 kW
kVA Dep.
A A A A
E4-08
0329h
Slip Compensation Gain
(Motor 2)
0.0 ~ 2.50
0.01
Cntrl Meth
R A A A
E4-09
033Fh
ASR Proportional Gain (Motor 2)
Cntrl Meth
0.01
Cntrl Meth
R A A A
E4-10
033Fh
ASR Integral Time (Motor 2)
0.000 ~ 10.000 Sec
0.001 Sec
Cntrl Meth
R A A A
E4-11
0326h
Torque Compensation Gain
(Motor 2)
0.00 ~ 2.50
0.01
1.00
R
A
A
A