Yaskawa G7 Modbus Communication User Manual
Page 60

60
Table 4.9 “F” Parameters
Access Level
Name
Address
Description
Data
Range
Unit
Default
During
Run
V/f
V/f
w/PG
OLV
FV
OLV2
1 Frequency
Reference
2 Output
Frequency
3 Output
Current
5 Motor
Speed
6 Output
Voltage
7 DC
Bus
Voltage
8 Output
Power
(kW)
9 Torque
Reference
15
Terminal A1 Level
16
Terminal A2 Level
17
Terminal A3 Level
18 Motor
Secondary
Current
19 Motor
Excitation
Current
20
Soft Starter (SFS) Output
21 ASR
Input
22 ASR
Output
24 PID
Feedback
26 Voltage
(Vq)
Reference
27 Voltage
(Vd)
Reference
32 ACR
(Iq)
Output
33 ACR
(Id)
Output
36 PID
Input
37 PID
Output
38 PID
Setpoint
42 Estimated
Motor
Flux
43
Id Compensation Value
44 ASR
Output
Without
Filter
45
Feed Forward Output
F4-01
0391h
AO-08/AO-12 Option Kit
Channel 1 Function Selection
48
Stabilizing Speed at
Regeneration (OLV2)
1
02h - - - - -
F4-02
0392h
AO-08/12 Channel 1 Gain
0.0 ~ 1000.0 %
0.1 %
100.0 %
R
A
A
A
A
A
F4-03
0393h
AO-08/12 Channel 2 Select
See
F4-01
1
03h A A A A A
F4-04
0394h
AO-08/12 Channel 2 Gain
0.0 ~ 1000.0 %
0.1 %
50.0 %
R
A
A
A
A
A
F4-05
0395h
AO-08/12 Channel 1 Bias
-110.0 ~ 110.0 %
0.1 %
0.0 %
R
A
A
A
A
A
F4-06
0396h
AO-08/12 Channel 2 Bias
-110.0 ~ 110.0 %
0.1 %
0.0 %
R
A
A
A
A
A
0 0-10
VDC
F4-07
0397h
AO-12 Channel 1
Signal Type Selection
1
-10 +10 VDC
1
0
A A A A A
0 0-10
VDC
F4-08
0398h
AO-12 Channel 2
Signal Type Selection
1
-10 +10 VDC
1
0
A A A A A