Run/stop and frequency reference source, Run/stop and frequency reference, Run/stop source – Yaskawa G7 Modbus Communication User Manual
Page 15: Frequency reference source

15
Run/Stop and Frequency Reference
The Run/Stop and Frequency Reference commands can originate from:
Serial communication (Built-in Modbus: Keypad or R+/-, S+/- Terminals)
Keypad (Digital Operator)
Terminal Strip
Option Card
Parameter B1-01 (Run/Stop Method Selection) allows the selection of the origin of the Run/Stop command. Parameter B1-02 (Reference
Selection) allows the selection of the origin of the Frequency Reference command. The Run/Stop and Frequency Reference commands may
have different origins.
For example, the Run/Stop command may be set to Terminals (B1-01=1) while the Frequency Reference command may be set to Serial
Communication (B1-02=2).
Run/Stop Source
Table 1.7 Run/Stop Method Selection
B1-01
Operation Method Selection (Run/Stop)
0 Keypad
1
Terminal Strip (Default Setting)
2
Serial Communication (Built-in Modbus: Keypad or R+/-, S+/- Terminals)
3
Option Card (EtherNet/IP, Modbus TCP/IP, DeviceNet, Profibus DP, LonWorks, etc.)
4
Pulse Input (RP Terminal)
Frequency Reference Source
Table 1.8 Frequency Reference Source Selection
B1-02
Frequency Reference Selection
0 Keypad
1
Terminal Strip (Default Setting)
2
Serial Communication (Built-in Modbus: Keypad or R+/-, S+/- Terminals)
3
Option Card (EtherNet/IP, Modbus TCP/IP, DeviceNet, Profibus DP, LonWorks, etc.)