Table 4.11 “L” Parameters
Access Level
Name
Address
Description
Data
Range
Unit
Default
During
Run
V/f
V/f
w/PG
OLV
FV
OLV2
0 Disabled
1
Standard Fan Cooled
2 Standard
Blower
Cooled
L1-01
0480h
Motor Overload (OL1)
Motor Selection
3 Vector
Duty
1
1
Q Q Q Q Q
L1-02
0481h
Motor Overload (OL1)
Time Constant
0.1 ~ 5.0 min
0.1 min
1.0 min
A
A
A
A
A
0
Ramp to Stop
1
Coast to Stop
2 Fast-Stop
(C1-09)
L1-03
0482h
Motor Overheat (OH3)
Alarm Selection
3 Alarm
Only
1
3
A A A A A
0
Ramp to Stop
1
Coast to Stop
L1-04
0483h
Motor Overheat (OH4)
Fault Selection
2 Fast-Stop
(C1-09)
1
1
A A A A A
L1-05
0484h
Motor Overheat Filter
Time
0.00 ~ 10.00 Sec
0.01 Sec
0.20 Sec
A
A
A
A
A
0 Disabled
1
Enabled - L2-02 Time
L2-01
0485h
Power Loss Ride Thru
Selection
2
Enabled - CPU Active
1
0
A A A A A
L2-02
0486h
Power Loss Ride Thru
Time
0.0 ~ 25.5 Sec
0.1 Sec
0.1 Sec
A
A
A
A
A
L2-03
0487h
Minimum Baseblock
Time
0.1 ~ 5.0 Sec
0.1 Sec
0.5 Sec
A
A
A
A
A
L2-04
0488h
Voltage Recovery Ramp
Time
0.0 ~ 5.0 Sec
0.1 Sec
0.3 Sec
A
A
A
A
A
L2-05
0489h
Undervoltage Detection
Level
kVA Dep.
1 VDC
kVA Dep.
A A A A A
L2-06
048Ah
KEB Decel Time
0.0 ~ 200.0 Sec
0.1 Sec
0.0 Sec
A
A
A
A
A
L2-07
048Bh
Powerloss Ride Thru
Accel Time
0.0 ~ 25.5 Sec
0.1 Sec
0.0 Sec
A
A
A
A
A
L2-08
048Ch
KEB Frequency Gain
0 ~ 300 %
1 %
100 %
A
A
A
A
A
0 Disabled
1 General
Purpose
L3-01
048Fh
Stall Prevention During
Accel Selection
2 Intelligent
1
1
A A A
L3-02
0490h
Stall Prevention During
Accel Current Level
0 ~ 200 %
1 %
150 %
A
A
A
L3-03
0491h
Stall Prevention During
Accel Constant HP Area
Current Lower Limit
0 ~ 100 %
1 %
50 %
A
A
A
0 Disabled
1 General
Purpose
2 Intelligent
L3-04
0492h
Stall Prevention During
Decel Selection
3
Enabled - Braking Resistor
1
1
Q Q Q Q Q
0 Disabled
1
Decel Time 1 (C1-02)
L3-05
0493h
Stall Prevention During
Run Selection
2
Decel Time 2 (C1-04)
1
1
A A
L3-06
0494h
Stall Prevention During
Run Current Level
30 ~ 200 %
1 %
160 %
A
A
0 Disabled
L3-11
04C7h
Overvoltage Inhibit
Selection
1 Enabled
1
0 A
A
A
L3-12
04C8h
Overvoltage Inhibit
Voltage Level
kVA Dep.
1 V
kVA Dep.
A
A
A
L4-01
0499h
Speed Agree Level
0.0 ~ 400.0 Hz
0.1 Hz
0.0 Hz
A
A
A
A
A
L4-02
049Ah
Speed Agree Width
0.0 ~ 20.0 Hz
0.1 Hz
2.0 Hz
A
A
A
A
A
L4-03
049Bh
Speed Agree Level +/-
-400.0 ~ 400.0 Hz
0.1 Hz
0.0 Hz
A
A
A
A
A
L4-04
049Ch
Speed Agree Width +/-
0.0 ~ 20.0 Hz
0.1 Hz
2.0 Hz
A
A
A
A
A
0 Stop
L4-05
049Dh
Frequency Reference
Loss Selection
1
Run at L4-06 x Previous
Reference
1
0
A A A A A
L4-06
04C2h
Frequency Reference
Loss Gain
0.0 ~ 100.0 %
0.1 %
80.0 %
A
A
A
A
A