Pclink, Serial – Yaskawa MP2000 Series User Manual
Page 31

Page 31
MP2000.02, 1/18/2011
Data subject to change without notice
Yaskawa America, Inc.
In addition, connection of a MEMOBUS master device to the serial port of the MP2000 series PCLINK-01 module
and MEMOBUS message communication via the PCLINK network are possible. The PCLINK–01 reception side has a
MEMOBUS message reception function. (When a MEMOBUS message is received via the serial port, CH5 is used by
the MSG-RCV function.) The controller on the transmission side does not need a ladder protocol. The MEMOBUS
messages received from the serial port will be automatically determined to be either received by the local CPU module
or transmitted on the PCLINK network according to the station address of the MEMOBUS protocol.
Figure 4.4 MEMOBUS Messaging Between the Controllers via the PCLINK Serial Port
* In cases of a GL40, 60, 70 and GL120/130 side message slave, the message reception function can be omitted.
The MEMOBUS protocol capable of being used in PCLINK transmission is as follows.
Function Code
Meaning
Data Address Setting
Range
Data Size
MEMOBUS
01H
Coil Status Readout
0 ~ 65535
1~2000 (No. of bits)
02H
Input Relay Status Readout
0 ~ 65535
1~2000 (No. of bits)
03H
Holding Register Content Readout
0 ~ 65534
1~125 (No. of words)
04H
Input Register Content Readout
0 ~ 32767
1~125 (No. of words)
05H
Single Coil Status Change
0 ~ 65535
Disabled
06H
Write to Single Holding Register
0 ~ 65534
Disabled
08H Loopback
Test
Disabled Disabled
0FH
Multiple Coil Status Change
0 ~ 65534
1~800 (No. of bits)
10H
Write to Multiple Holding Registers
0 ~ 65534
1~100 (No. of words)
In PCLINK transmission, the transmission target can be designated by the group number in addition to the station
number in the message transmission target. In group number designation, it is possible to multicast messages to
stations with the same group number. However, the available messages are limited to the write series.
ÁÂÃÄÅÆÇÈÉ
Á
Â
Ã
Ä
Å
Æ
ÇÈ
ÁÂÃÄÅÆÇÈÉ
Á
Â
Ã
Ä
Å
Æ
ÇÈ
PCLINK
MEMOBUS command path
ÁÂÃ
ÄÂÅ
ÆÇÈ
ÁÂÃ
ÄÉ
ÆÇ
ÁÂÃÄ
É
ÆÇ
ÇÈ
Serial
MEMOBUS
Master Device
Serial
ÁÂÃÄ
ÂÅ
ÆÇÈ
Automatically
switches according to
the address number
É
É
The MEMOBUS protocol address
settings are transferred to the local
CPU if other than the PCLINK
station number address of the local
station
The MEMOBUS protocol address
settings are streamed on the PCLINK
network if other than the PCLINK
station number address of the local
station