Yaskawa Varispeed-686SS5 CIMR-SSA User Manual
Page 87

88
Table A−5 Constants List (Cont’d)
Constant
No.
Name
Initial
Setting
User
Setting
Constant
No.
Name
Initial
Setting
User
Setting
L1-01
Motor protection selection
1
o1-01
Monitor selection
6
L1-02
Motor protection time
60.0
o1-02
Monitor selection after power up
1
L2-01
Momentary power loss detection
0
o1-03
Units of speed reference setting and
monitor
1
L2-02
Momentary power loss ridethru time
*1
o2-01
LOCAL/REMOTEkeyenable/disable
1
L2-03
Deceleration time at momentary pow-
er loss
30.0
o2-02
STOP key during control circuit termi-
nal operation
0
L2-05
Undervoltage detection level
190
*2
o2-04
kVA selection
*1 *5
L3-01
Overvoltage prevention function
selection
*3
1
o2-05
Speed reference setting method selec-
tion
0
L4-01
Speed detection level
0.0
o2-06
Operation selection when digital opera-
tor is disconnected
0
L4-02
Speed detection width
2.0
o2-07
Cumulative operation time setting
L4-03
Speed detection level (+/-)
0.0
o2-08
Cumulative operation time selection
0
L4-04
Speed detection width (+/-)
2.0
T1-02
Tuning mode
0
L4-05
Operation when speed reference is
missing
0
T1-03
Tuning item selection
1
L5-01
Number of auto restart attempts
0
L5-02
Auto restart operation selection
0
L6-01
Torque detection selection 1
0
L6-02
Torque detection level 1
150
L6-03
Torque detection time 1
0.1
L6-04
Torque detection selection 2
0
L6-05
Torque detection level 2
150
L6-06
Torque detection time 2
0.1
L7-01
Forward torque limit
160
L7-02
Reverse torque limit
160
L7-03
Forward regenerative torque limit
160
L7-04
Reverse regenerative torque limit
160
L8-01
Protect selection for internal DB resis-
tor
*4
0
L8-02
Inverter overheat pre-alarm level
95
L8-03
Operation selectionafter inverterover-
heat pre-alarm
3
L8-05
Input open-phase protection selection
0
L8-07
Output open-phase protection selec-
tion
0
L8-10
Ground fault protection selection
1
L9-01
Step-out protection selection
1
L9-02
Output current unbalance protection
selection
*6
1
*1
Setting range and initial setting differ depending on inverter capacity.
*2
Set value for 200V class. For 400V class, the value is twice as that of 200V class.
*3
When using a braking resistor unit, set L3-01 to “0.”
*4
When using a mounting-type braking resistor unit (model ERF), set L8-01 to “1.”
*5
Not initialized.
*6
The display is applicable for software No. 1033 or later (FLASH side). To check which
version is being used, refer to U1-14.