Constant Initialization

All the constants are returned to the initial setting by initialization. Several constants such as motor
constants cannot be initialized. For details, refer to APPENDIX 4.

Table 26

Constant Initialization

Step

Description

Key Sequence

Digital Operator Display

Remarks

Displaying speed reference

G

1

Move to program mode.

DRIVE

PRGM

Constant No. display

Displays the constant No. selected
formerly.

2

Select A1-03.

RESET

3

Display the set value.

DATA

ENTER

4

Input 2220.

RESET

5

Write-in the value.

DATA

ENTER

Displays for 0.5 seconds.

Display return to 0.

6

Return to constant No. display.

DSPL

6

Return to drive mode.

DRIVE

PRGM

G

Speed reference return to 0.