Table 6 400v class wire size – Yaskawa Varispeed-686SS5 CIMR-SSA User Manual
Page 33

34
Table 6
400V Class Wire Size
Circuit
Model
CIMR-
Terminal Symbol
Terminal
Screw
Wire Size *
mm
2
Wire Type
SSA40P4
R, S, T, © , ¨ 1 , ¨ 2, B1, B2, U, V, W
M4
2 to 5 5
SSA40P4
M4
2 to 5.5
SSA40P7
R, S, T, © , ¨ 1 , ¨ 2, B1, B2, U, V, W
M4
2 to 5 5
SSA40P7
M4
2 to 5.5
SSA41P5
R, S, T, © , ¨ 1 , ¨ 2, B1, B2, U, V, W
M4
2 to 5 5
SSA41P5
M4
2 to 5.5
SSA42P2
R, S, T, © , ¨ 1 , ¨ 2, B1, B2, U, V, W
M4
2 to 5 5
SSA42P2
M4
2 to 5.5
SSA43P7
R, S, T, © , ¨ 1 , ¨ 2, B1, B2, U, V, W
M4
2 to 5.5
SSA43P7
M4
3.5 to 5.5
SSA45P5
R, S, T, © , ¨ 1 , ¨ 2, B1, B2, U, V, W
M4
3 5 to 5 5
SSA45P5
M4
3.5 to 5.5
SSA47P5
R, S, T, © , ¨ 1 , ¨ 2, B1, B2, U, V, W
M5
5 5
SSA47P5
M5
5.5
SSA4011
R, S, T, © , ¨ 1 , ¨ 2, B1, B2, U, V, W
M5
8 to 14
SSA4011
M6
8
SSA4015
R, S, T, © , ¨ 1 , ¨ 2, B1, B2, U, V, W
M5
8 to 14
SSA4015
M6
8
R, S, T, © , ¨ 1 , ¨ 2, ¨ 3, U, V, W
M6
14
SSA4018
M8
8
SSA4018
r ,
M4
0.5 to 5.5
R, S, T, © , ¨ 1 , ¨ 2, ¨ 3, U, V, W
M6
22
SSA4022
M8
8
SSA4022
r ,
M4
0.5 to 5.5
R, S, T, © , ¨ 1 , ¨ 2, ¨ 3, U, V, W
M8
22
SSA4030
M8
8
SSA4030
r ,
M4
0.5 to 5.5
R, S, T, © , ¨ 1 , ¨ 2, ¨ 3, U, V, W
M8
30
Power cable:
Main
SSA4037
M8
14
Power cable:
600V vinyl sheathed
Main
SSA4037
r ,
M4
0.5 to 5.5
600V vinyl sheathed
wire or equivalent
R, S, T, © , ¨ 1 , ¨ 2, ¨ 3, U, V, W
M8
50
q
SSA4045
M8
14
SSA4045
r ,
M4
0.5 to 5.5
R, S, T, U, V, W
M10
38 to 100
SSA4055
©
, ¨ 3
M8
SSA4055
M8
22
r , 200, 400
M4
0.5 to 5.5
R, S, T, U, V, W
M10
38 to 100
SSA4075
©
, ¨ 3
M8
SSA4075
M8
22
r , 200, 400
M4
0.5 to 5.5
R, S, T, U, V, W
M10
60 to 100
SSA4110
©
, ¨ 3
M8
SSA4110
M8
30
r , 200, 400
M4
0.5 to 5.5
R, S, T, U, V, W
M12
100 to 200
SSA4160
©
, ¨ 3
M8
SSA4160
M8
50
r , 200, 400
M4
0.5 to 5.5
SSA4220
R, S, T, © , ¨ 1 , ¨ 3, U, V, W
M16
325 or
200 × 2P
SSA4220
M8
60
r , 200, 400
M4
0.5 to 5.5
SSA4300
R, S, T, © , ¨ 1 , ¨ 3, U, V, W
M16
250 × 2P or
325 × 2P
SSA4300
M8
60
r , 200, 400
M4
0.5 to 5.5
Control
Common to all
models
1 to 33
M3.5
0.5 to 2
Twisted shielded wire
* Wire size is determined using 75_C temperature-rated copper wire.
When connecting a braking resistor unit or a braking unit, select wire size referring to the
instructions of braking resistor unit and braking unit (manual No.: TOE-C726-2).