2 braking unit and braking resistor unit – Yaskawa Varispeed-686SS5 CIMR-SSA User Manual
Page 76

APPENDIX 3 TYPICAL CONNECTION DIAGRAM
77
3.2
BRAKING UNIT AND BRAKING RESISTOR UNIT
For models CIMR-SSA2011, -SSA2015 (200 V Class 11, 15 kW)
1 Forward Run
when CLOSED
17 (Aux Speed Ref. at
Factory Setting)
15 Speed Setting Power
Supply +15V 20mA
3
4
5
6
7
8
Braking Unit
3
4
21
22
Analog
Monitor 1
(12)
Ground (100Ω or less)
Braking Unit
(Option)
P
B
Braking Resistor
Unit (Option) [
1
2
Overload Relay Trip Contact
Level
Detection
3-Phase
Power Supply
200 to 230 V
50/60 Hz
11
0 V
3
4
23
¨
1
VS-686SS5
MCCB
R
MC
R (L1)
S
S (L2)
T
T (L3)
THRX OFF
ON
MC
SA
Overload Relay Trip Contact
of Braking Resistor Unit
1
2
MC
TRX
TRX
20 18
Fault
Contact
¨
2
©
SA
SA
THRX
U (T1)
V (T2)
W (T3)
Motor
M
MC
DC Reactor
(Option):
¨
3
+
AM
+
−
Multi-function Analog Output
-10 to +10V 2mA
(Output Current at Factory
Setting)
SM
Multi-function Analog Output
-10 to +10 V 2mA
(Rotation Speed at Factory
Setting)
−
Forward Run/Stop
Reverse Run/Stop
Factory
Setting
External Fault
Fault Reset
Multi-step Speed Setting 1
(Master/Aux Change)
Multi-step Speed
Setting 2
Jog Reference
External Baseblock
2 Reverse Run
when CLOSED
Multi-function
Contact Input
Sequence Common
Terminal (0V)
12
Shield Sheath
Connection Terminal
13 Master Speed Ref.
0 to 10V (20kΩ)
14 Master Speed Ref.
4 to 20mA (250Ω)
16 Multi-function Analog Input
0 to 10V (20kΩ)
33 Speed Setting Power Supply
-15V 20mA
Multi-function Open
Collector Output
48 V 50 mA or less
Multi-function
Output Common
27
Open Collector 2
(Speed Agree Signal
at Factory Setting)
26
Open Collector 1
(Zero Speed Signal at
Factory Setting)
25
Multi-function Contact Output
250 VAC 1 A or less
30 VDC 1A or less
(Signal during Running at Factory
Setting)
10
9
20
19
Fault Contact Output
250 VAC 1 A or less
30 VDC 1 A or less
18
2 kΩ
2 kΩ
0 to +10 V
4 to 20 mA P
0 to +10 V
P
0 V
P
External
Speed
Reference
Analog
Monitor 2
[
When using the braking resistor unit, set constant L3-01 to “0” (overvoltage prevention selection
is disabled). If it is not changed, the inverter may not stop within set decel time.
Use sequencer to break
power supply side on
overload relay trip contact
of braking resistor unit.
:
When installing a DC reactor (option), remove the common bar between ¨1 and ¨2 terminals
(provided as standard) and connect a DC reactor with the terminals.
Short-circuit
Bar
¨
¨
0
©
0
©
18
20