APPENDIX 1 SPECIFICATIONS

73

Table A-2

Constant Torque Series Specifications

Model

SST4-

Mounting Method

Foot-mounted type, flange-mounted type

Enclosure

Totally-enclosed type, totally-enclosed externally-cooled type (IP44)

r Rated min

-1

1750 min

-1

1450 min

-1

1150 min

-1

M

otor Output Range

200V class

0.4 to 75 kW

0.4 to 75 kW

0.4 to 75 kW

M

o Output Range

400V class

0.4 to 300 kW

0.4 to 250 kW

0.4 to 200 kW

Speed Control Range (Continuous)

1:500 (Constant torque) (Refer to * for constant output range.)

Time Rating

Continuous

Insulation Class

Class F

Sensor

With PG

S

upply

Input Voltage

200V class: 200/208/220V 50Hz, 200/208/220/230V 60Hz

400V class: 400/415/440/460V 50/60Hz

w

er

S

Allowable Voltage Fluctuation

+10% to -15%

Po

w

Allowable Frequency Fluctuation

± 5%

Control Method

Flux vector

Starting Torque

150%

Speed Control Range

1:500

cs

Speed Control Accuracy

± 0.02%

istic

s

Torque Limit

Provided

cteri

s

Torque Accuracy

± 5%

arac

t

Run Speed Resolution

Digital command: 0.01%

Ch

a Run Speed Resolution

Analog command: 0.05% (11 bit + code)

ntrol

C

Overload Capacity

150% of rated output current for one minute

C

ont Run Speed Setting Signal

-10 to 10V, 0 to 10V, 4 to 20mA

C

Accel/decel Time

0 to 6000 seconds

erter

Main Functions

PID control, overtorque detection, torpue limit, multi-step speed operation,

accel/decel time change, 3-wire sequence, speed control/torque control change

auto-tuning

nve

r

Motor Overload Protection

Protected by electronic thermal overload relay

In

Instantaneous Overcurrent

Motor coasts to a stop at approx. 200% of inverter rated current.

Blown Fuse Protection

Motor coasts to a stop by blown-fuse.

ns Overload

Motor coasts to a stop after one minute at 150% of rated output current.

F

unctio

n

Overvoltage

200V class: Motor coasts to a stop if main-circuit voltage exceeds 406V.
400V class: Motor coasts to a stop if main-circuit voltage exceeds 812V.

ective

F

u

Undervoltage

200V class: Motor coasts to a stop if main-circuit voltage drops to 190V or below.
400V class: Motor coasts to a stop if main-circuit voltage drops to 380V or below.

rote

c

Heatsink Overheat

Protected by thermistor

Pr

o

Stall Prevention
(Overvoltage Prevention)

Stall prevention during deceleration

Ground Fault

Protected by electronic circuit

Power Charge Indication

Charge LED stays ON until bus voltage drops below 50V.

Location

Indoor (protected from corrosive gases and dust)

ent Humidity

90% RH or less (non-condensing)

onm

e

Storage Temperature

-20°C to +60°C

viro

n

Ambient Temperature

-10°C to +40°C (Enclosed wall-mounted type), -10°C to +45°C (Open chassis type)

En

v

Elevation

1000 m or less

Vibration

9.8 m/s

2

(1G) at 10 to less than 20 Hz, up to 2 m/s

2

(0.2G) at 20 to 50 Hz

*Constant output range is as follows:

1750 min

-1

1450 min

-1

1150 min

-1

1:1.5 (0.4 to 75 kW)

1:1.3 (90 to 160 kW)

1:1.2 (200 to 300 kW)

1:1.5 (0.4 to 55 kW)

1:1.3 (75 to 160 kW)

1:1.2 (200 to 250 kW)

1:1.5 (0.4 to 45 kW)

1:1.3 (55 to 160 kW)

1:1.2 (200 kW)

Note: Constant torque series cannot be used to the following applications:

• Commercial power supply / inverter power supply switch operation
• One inverter drives several motors (multi-motor drive).