4.5 Regenerative Resistor Selection

49

Regenerative Unit Specifications

SGDG-04GT

The SGDG-04GT has terminals for connecting an external regen resistor of higher
capacity. However, the SGDG-04GT does not automatically recognize this external regen
resistor and it doesn’t activate the regen IGBT. Thus, when an external resistor is
connected, the regen energy is still processed by internal regen capacity. The alarm #4
(overvoltage) will occur if the regen energy is too high. To add external regen capability
to the SGDG-04GT, one of the following methods may be used:

1. Use external regen unit JUSP-RG08D. Refer to the information in the

table above for more details. When this external regen unit is used, #5
of SW1 in the SGDG-04GT should be turned OFF to avoid erroneous
alarms.

or

2. Use SGDG-04GTY22P for external regen application only. If the user knows that the

application requires extra regen capacity, the Y-mod unit must be ordered. With
Y22P-mod, two (2) external regen resistors, RH500N25_ohmK, wired in series must
be connected to the SGDH-04GT at all times. These resistors should be connected
across terminals B1 and B2. The convection cool capacity of these two resistors in
series is 120W. The capacity increases to 300W with forced-air cooling. Therefore,
the items required are:

1 x SGDG-04GTY22P
2 x RH500N25_ohmK

Type

JUSP-RG08

JUSP-RG08D

Remarks

Applicable Servopack

SGDG Servopack

Regenerative Working Voltage

380Vdc

Regenerative Processing Current

8Adc

Regenerative resistance:50

60W

Error Detection Function

Regenerative resistance

disconnection, regenerative

transistor fault, overvoltage

Alarm Output

Normally closed contact (open

when protective function

operates)

200V operation ok

Dimensions in mm

(inches)

55W x 160H x 130D

(2.17W x 6.30H x 5.31D)