4.2 Protection Sequence Design

43

DB OFF Input

Sequence Input Signal: The basic connection and handling method for the (DB OFF)
signal is shown below. This is used to forcibly release the “DB stop state” during Servo
OFF from the upper-level device.

Switches the motor between a powered and a non-powered state.

RUN Signal Output

Photocoupler Output Signal: The basic connection method and handling method for the
“RUN” signal is shown below. This output signal indicates that the base block on the
output inverter is released, and power is being applied to the motor.

Input DB OFF

 

CN1-15

DB OFF

When

ONCN1-15

is “L” level

DB stop at Servo OFF

DB ON

DB Stop State

DB stop at Servo OFF

When

OFFCN1-15

is “H” level

Releases the DB stop and goes to

free run at Servo OFF

DB OFF

DB Stop Release

Release DB stop

according to an input

signal

Output

RUN

 

CN1-7

RUN Signal Output

ON State

CN1–7, 10 is “closed”

CN1–7 is level “L”

Base Block

OFF State

CN1–7, 10 is “open” CN1–

7 is level “H”

Base Block Released

24V Power

+24V

+24VIN

Amplifier

CN1-13

3.3k

Ω

Photocoupler

Upper-Level

Device

DB-OFF

CN1-15

5mA

0V

Photocoupler Output per
Output

Max. Use Voltage:

DC30V

Max. Output Current:

DC50mA

Digital Torque Amplifier

C N 1-7

C N 1-10

R U N

+

R U N

-

24V Power

+24V

0V