4.2 Protection Sequence Design
43
■
DB OFF Input
Sequence Input Signal: The basic connection and handling method for the (DB OFF)
signal is shown below. This is used to forcibly release the “DB stop state” during Servo
OFF from the upper-level device.
Switches the motor between a powered and a non-powered state.
■
RUN Signal Output
Photocoupler Output Signal: The basic connection method and handling method for the
“RUN” signal is shown below. This output signal indicates that the base block on the
output inverter is released, and power is being applied to the motor.
→
Input DB OFF
CN1-15
DB OFF
When
ONCN1-15
is “L” level
DB stop at Servo OFF
DB ON
DB Stop State
DB stop at Servo OFF
When
OFFCN1-15
is “H” level
Releases the DB stop and goes to
free run at Servo OFF
DB OFF
DB Stop Release
Release DB stop
according to an input
signal
Output
→
RUN
CN1-7
RUN Signal Output
ON State
CN1–7, 10 is “closed”
CN1–7 is level “L”
Base Block
OFF State
CN1–7, 10 is “open” CN1–
7 is level “H”
Base Block Released
24V Power
+24V
+24VIN
Amplifier
CN1-13
3.3k
Ω
Photocoupler
Upper-Level
Device
DB-OFF
CN1-15
5mA
0V
Photocoupler Output per
Output
Max. Use Voltage:
DC30V
Max. Output Current:
DC50mA
Digital Torque Amplifier
C N 1-7
C N 1-10
R U N
+
R U N
-
24V Power
+24V
0V