Drive parameters - continued – Yaskawa V7N Drive with DeviceNet User Manual
Page 29

29
PARA- ADDR CLASS 100
NAME
DATA
SETTING RANGE
SETTING
FACTORY
METER
INST. 01
(AND UNITS)
INCREMENT SETTING
Analog Frequency Reference
n070 146h
46h
Filter Time Constant
-
0.00 to 2.00
0.01 s
0.10
(CN2, Voltage Ref Input)
n071 147h
47h
Analog Frequency Reference
-
-255 to 255
1%
100
Gain (CN2, Current Ref Input)
n072 148h
48h
Analog Frequency Reference
-
-100 to 100
1%
0
Bias (CN2, Current Ref Input)
Analog Frequency Reference
n073 149h
49h
Filter Time Constant
-
0.00 to 2.00
0.01 s
0.10
(CN2, Current Ref Input)
0
0: Multi-Function analog input disabled
1
1: Aux. Frequency reference
n077 14Dh
4Dh
Multi-Function Analog
2
2: Frequency gain
1
0
Input CN2 Selection
3
3: Frequency bias
4
4: Voltage bias
n078 14Eh
4Eh
Multi-Function Analog Input
0
0: 0 - 10V
1
0
Signal Selection
1
1: 4 - 20 mA
n079 14Fh
4Fh
Multi-Function Digital Input
0
0: Scans twice with 8 msec scan rate
1
0
Scan Rate Selection
1
1: Scans twice with 2 msec scan rate
n080 150h
50h
Carrier Frequency
-
1 to 4 (x 2.5 kHz)
1
3
7 to 9 (synchronous)
0
0: Not Provided
1
1: Continuous operation after power
n081 151h
51h
Momentary Power Loss
recovery within 2 sec.
1
0
Ride-through Method
2
2: Continuous operation after power
recovery within control logic time
(no fault output)
n082 152h
52h
Number of auto restarts
-
0 to 10
1
0
attempts
n083 153h
53h
Prohibit Frequency 1
-
0.00 to 400.0
0.01 (Hz)
0.00
or 0.1 (Hz)
n084 154h
54h
Prohibit Frequency 2
-
0.00 to 400.0
0.01 (Hz)
0.00
or 0.1 (Hz)
n085 155h
55h
Prohibit Frequency 3
-
0.00 to 400.0
0.01 (Hz)
0.00
or 0.1 (Hz)
n086 156h
56h
Prohibit Frequency Deadband
-
0.00 to 25.50
0.01 (Hz)
0.00
n087 157h
57h
Elapsed Time Function
0
0: Time elapses when power is On
0
Selection
(5)
1
1: Time elapses when Drive is running
n088 158h
58h
Elapsed Operation Time
-
0 to 9999 hours
0
(Initial Value)
(5)
n089 159h
59h
DC Injection Current
-
0 to 100
1 (%)
50
n090 15Ah
5Ah
DC Injection Time at stop
-
0.0 to 25.5
0.1 (sec)
0.0
n091 15Bh
5Bh
DC Injection Time at start
-
0.0 to 25.5
0.1 (sec)
0.0
n092 15Ch
5Ch
Stall Prevention During
0
0: Enabled
1
0
Deceleration
1
1: Disabled
n093 15Dh
5Dh
Stall Prevention During
-
30 to 200
1 (%)
170
Acceleration
n094 15Eh
5Eh
Stall Prevention Level During
-
30 to 200
1 (%)
160
Running
n095 15Fh
5Fh
Frequency Detection Level
-
0.00 to 400.0
0.01 (Hz)
0.00
or 0.1 (Hz)
Drive Parameters - Continued
Section 9
Drive Parameter Listing
(n070-n095)
IG.V7N.qxd:IG.V7N.qxd 6/5/07 3:22 AM Page 29