Drive parameters - continued – Yaskawa V7N Drive with DeviceNet User Manual
Page 28

28
PARA- ADDR CLASS 100
NAME
DATA
SETTING RANGE
SETTING
FACTORY
METER
INST. 01
(AND UNITS)
INCREMENT SETTING
9
9:
Multi-step speed ref. cmd. D
n053 135h
35h
Multi-function Input Selection 4
Ah
10: JOG Selection
1
5
(Terminal S4)
Bh
11: Accel/Decel time change cmd.
(5)
Ch
12: External Base Block (N.O.)
n054 136h
36h
Multi-function Input Selection 5
Dh
13: External Base Block (N.C.)
1
6
(DeviceNet Input S5)
Eh
14: Speed search from max. freq.
(6)
Multi-function Input Selection 6
Fh
15: Speed search from set freq.
n055 137h
37h
(DeviceNet Input S6)
10h
16: Accel/Decel hold command
1
7
11h
17: Remote/Local selection
(7)
12h
18: Communication / control circuit terminal
selection
13h
19: Fast Stop - Fault (N.O.)
14h
20: Fast Stop - Alarm (N.O.)
15h
21: Fast Stop - Fault (N.C.)
Multi-function Input Selection 7
16h
22: Fast Stop - Alarm (N.C.)
1
10
n056 138h
38h
(DeviceNet Input S7)
17h
23: PID control off
(10)
18h
24: I value reset (PID)
19h
25: I value hold (PID)
1Ah
26: Over Heat Pre-alarm OH3
1Bh
27: Accel/Decel Time Select 2
1Ch 28: Data input from DeviceNet communications
22
34: Up/Down Function
0
0:
Fault
Multi-Function Output
1
1:
During running
n057 139h
39h
Selection 1 (DeviceNet
2
2:
Speed Agree
1
0
Output MA)
3
3:
Zero Speed
4
4:
Frequency detection 1
5
5:
Frequency detection 2
6
6:
Overtorque detection (N.O.)
7
7:
Overtorque detection (N.C.)
Multi-Function Output
8
8:
Undertorque Detection (N.O.)
n058 13Ah
3Ah
Selection 2
9
9:
Undertorque Detection (N.C.)
1
1
(Terminals P1 & PC)
Ah
10: Minor Fault
Bh
11: During Base Block
Ch
12: Local / Remote
Dh
13: Ready
Eh
14: During auto restart
Fh
15: During undervoltage
Multi-Function Output
10h
16: During reverse run
n059 13Bh
3Bh
Selection 3
11h
17: During speed search
1
2
(Terminals P2 & PC)
12h
18: Comm. Controlled
13h
19: PID feedback loss
14h
20: Frequency Reference Loss Detect (N.O.)
15h
21: Overheat Pre-alarm OH3 (N.O.)
n064 140h
40h
Frequency Reference Loss
0
0:
No Detection
1
0
Detection
1
1:
Continue to run at 80% of max. frequency
n068 144h
44h
Analog Frequency Reference
-
-255 to 255
1%
100
Gain (CN2, Voltage Ref Input)
n069 145h
45h
Analog Frequency Reference
-
-100 to 100
1%
0
Bias (CN2, Voltage Ref Input)
Drive Parameters - Continued
Section 9
Drive Parameter Listing
(n053-n069)