Specifications
Table 15 Option Specifications
Item
Specification
Model
SI-EM3
Supported Messages
• Read Multiple Registers (03H)
• Write Single Register (06H)
• Write Multiple Registers (10H)
• Read and Write Registers (17H)
Commands that support multiple registers have a maximum Read and Write size of 16
registers.
Option Conformance
Modbus-IDA Passed
Connector Type
RJ45 8-pin Shielded Twisted Pair Cat 5e cable
Physical Layer Type
Isolated Physical Layer
IP Address Setting
Programmable from drive keypad or network
Communication Speed
Programmable from drive keypad or network:
10/100 Mbps, auto-negotiate.
Number of Connections
Modbus TCP/IP: 10
Web Page Access: 2
Duplex Mode
Half-forced, Auto-negotiate, Full-forced
Address Startup Mode
Static, BOOTP, DHCP
Ambient Temperature
-10
°C to +50 °C (14 °F to 122 °F)
Humidity
95% RH or lower with no condensation
Storage Temperature
-20
°C to +60 °C (-4 °F to 140 °F) allowed for short-term transport of the product
Area of Use
Indoor (free of corrosive gas, airborne particles, etc.)
Altitude
1000 m (3280 ft.) or lower
Modbus_IM_E_conditional.fm 49 ページ 2012年10月31日 水曜日 午後1時45分