6 Related Drive Parameters
6
Related Drive Parameters
The following parameters are used to set up the drive for operation with the option.
Parameter setting instructions can be found in the drive Quick Start Guide or Technical
Manual.
Confirm proper setting of all the parameters in
using the digital operator, before
starting network communications.
Table 5 Related Parameter Settings
No.
(Addr. H)
Name
Description
Values
b1-01
(180)
Frequency
Reference
Selection
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option
4: Pulse Input (Terminal RP)
Default: 1
Range: 0 to 4
(Set to 3)
b1-02
(181)
Run Command
Selection
Selects the run command input source.
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S1 to S8
2: MEMOBUS/Modbus communications
3: Option
Default: 1
Range: 0 to 3
(Set to 3)
F6-01
(3A2)
Operation
Selection after
Communications
Error
Determines drive response when a bUS error is detected during
communications with the option.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Default: 1
Range: 0 to 3
F6-02
(3A3)
External Fault
Detection
Conditions (EF0)
Sets the condition for external fault detection (EF0).
0: Always detected
1: Detected only during operation
Default: 0
Range: 0, 1
F6-03
(3A4)
Stopping Method
for External
Fault from the
Communication
Option
Determines drive response for external fault input (EF0) detection
during option communications.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Default: 1
Range: 0 to 3
F6-06
(3A7)
Torque
Reference/
Torque Limit
Selection from
the
Communication
Option
0: Torque Reference/Torque Limit via network communications
are disabled
1: Torque Reference/Torque Limit via network communications
are enabled
Default: 0
Range: 0, 1