4 Option Components
12
YASKAWA ELECTRIC TOBP C730600 57B 1000-Series Option SI-EM3 Installation Manual
◆
Option LED Display
The option has four LEDs:
Bi-color Status LEDs:
• Module status (MS) red/green
• Network status (NS) red/green
Green Ethernet LEDs:
• Network speed-10/100 (MS) green
• Link status and network activity-Link/Act (NS) red/green
The operational states of the option LEDs after the power-up diagnostic LED sequence is
completed are described in
. Wait at least 2 seconds for the power-up diagnostic
process to complete before verifying the states of the LEDs.
Table 4 Option LED States
Name
<1> Remove the drive front cover to check the status of the LED. Be careful not to touch the main circuit terminals or
the control board in the drive.
Indication
Operating Status
Remarks
Color
Status
MS
–
OFF
Power supply OFF
Power is not being supplied to the drive
Green
ON
Option operating
The option is operating normally
Green
Flashing
Option initializing
The option is configuring an IP address
Red
ON
Fatal error occurred
The option has detected a fatal
(unrecoverable) error
Red
Flashing
Non-fatal error occurred
The option has detected a non-fatal
(recoverable) error
NS
–
OFF
Offline or power supply OFF
–
Green ON
Online communications
established
The option is online and has established
connections
Green
Flashing Control
connection
active
The option is online and has an established
and active control connection.
Red
ON
Communications error (fatal)
The option detected a duplicate IP address
10/100
Green
OFF
10 Mbps is established
–
Green
ON
100 Mbps is established
LINK/ACT
Green
OFF
Link is not established
Green
ON
Link is established
Green
Flashing
Link is established and there is
network activity
Modbus_IM_E_conditional.fm 12 ページ 2012年10月31日 水曜日 午後1時45分