beautypg.com

7 modbus tcp/ip messaging – Yaskawa Modbus TCP/IP Installation User Manual

Page 37

background image

7 Modbus TCP/IP Messaging

YASKAWA ELECTRIC TOBP C730600 57B 1000-Series Option SI-EM3 Installation Manual

37

2009

C0

Error Signal 1

0

Reserved

1

Undervoltage (Uv1)

2

Control Power Supply Undervoltage (Uv2)

3

Soft Charge Circuit Fault (Uv3)

4

Reserved

5

Ground Fault (GF)

6

Overcurrent (oC)

7

Overvoltage (ov)

8

Heatsink Overheat (oH)

9

Heatsink Overheat (oH1)

A

Motor Overload (oL1)

B

Drive Overload (oL2)

C

Overtorque Detection 1 (oL3)

D

Overtorque Detection 2 (oL4)

E

Dynamic Braking Transistor Fault (rr)

F

Braking Resister Overheat (rH)

200A

C1

Error Signal 2

0

External Fault at input terminal S3 (EF3)

1

External Fault at input terminal S4 (EF4)

2

External Fault at input terminal S5 (EF5)

3

External Fault at input terminal S6 (EF6)

4

External Fault at input terminal S7 (EF7)

5

External Fault at input terminal S8 (EF8)

6

Cooling fan Error (FAn)

7

Overspeed (os)

8

Excessive Speed Deviation (dEv)

9

PG Disconnected (PGo)

A

Input Phase Loss (PF)

B

Output Phase Loss (LF)

C

Motor Overheat (PTC input) (oH3)

D

Digital Operator Connection Fault (oPr)

E

EEPROM Write Error (Err)

F

Motor Overheat Fault (PTC input) (oH4)

Address

(hex)

Drive

Register

(hex)

Description

Bit

Description

Modbus_IM_E_conditional.fm 37 ページ 2012年10月31日 水曜日 午後1時45分

This manual is related to the following products: