9 Troubleshooting
YASKAWA ELECTRIC TOBP C730600 57B 1000-Series Option SI-EM3 Installation Manual
45
LED Operator Display
Fault Name
oFA04
Option Card Error (CN5-A)
Option flash write mode.
Cause
Possible Solution
Option hardware fault
Replace the option.
LED Operator Display
Fault Name
to
oFA30 to
oFA43
Option Card Connection Error (CN5-A)
Communication ID error.
Cause
Possible Solution
Option hardware fault
Replace the option.
LED Operator Display
Fault Name
oFb00
Option Card Connection Error (CN5-B)
Non-compatible option is connected.
Cause
Possible Solution
Non-compatible option
connected to the drive.
Connect the correct option to CN5-A.
LED Operator Display
Fault Name
oFb02
Option Card Fault (CN5-B)
Two of the same options are connected at the same time.
Cause
Possible Solution
Options AI-A3 or DI-A3
were connected to the
CN5-B port while an
option was already
connected to CN5-A.
• Only one type of AI-A3, DI-A3 or SI- option can be connected to the drive.
• The SI-EM3 option can only be connected to CN5-A.