9 Troubleshooting

YASKAWA ELECTRIC TOBP C730600 57B 1000-Series Option SI-EM3 Installation Manual

45

LED Operator Display

Fault Name

oFA04

Option Card Error (CN5-A)
Option flash write mode.

Cause

Possible Solution

Option hardware fault

Replace the option.

LED Operator Display

Fault Name

to

oFA30 to

oFA43

Option Card Connection Error (CN5-A)

Communication ID error.

Cause

Possible Solution

Option hardware fault

Replace the option.

LED Operator Display

Fault Name

oFb00

Option Card Connection Error (CN5-B)
Non-compatible option is connected.

Cause

Possible Solution

Non-compatible option
connected to the drive.

Connect the correct option to CN5-A.

LED Operator Display

Fault Name

oFb02

Option Card Fault (CN5-B)
Two of the same options are connected at the same time.

Cause

Possible Solution

Options AI-A3 or DI-A3
were connected to the
CN5-B port while an
option was already
connected to CN5-A.

• Only one type of AI-A3, DI-A3 or SI-†† option can be connected to the drive.
• The SI-EM3 option can only be connected to CN5-A.