9 Troubleshooting
46
YASKAWA ELECTRIC TOBP C730600 57B 1000-Series Option SI-EM3 Installation Manual
■
Minor Faults and Alarms
LED Operator Display
Fault Name
oFC00
Option Card Connection Error (CN5-C)
Non-compatible option is connected.
Cause
Possible Solution
Non-compatible option
connected to the drive.
Connect the correct option to CN5-A.
LED Operator Display
Fault Name
oFC02
Option Card Fault (CN5-C)
Option flash write mode.
Cause
Possible Solution
Options AI-A3 or DI-A3
are connected to the
CN5-B port with an
option connected to CN5-
A.
• Only one type of AI-A3, DI-A3 or SI- option can be connected to the drive.
• The SI-EM3 option can only be connected to CN5-A
LED Operator Display
Minor Fault Name
CALL
Serial Communication Transmission Error
Communication is not established.
Cause
Possible Solution
Minor Fault
(H2- = 10)
Communication wiring is
faulty, there is a short
circuit, or improper
connection
Check for wiring errors:
• Correct the wiring
• Remove ground shorts and reconnect loose wires
YES
Programming error on the
master side
Check communications at start-up and correct programming errors.
Communication circuitry
is damaged.
• Perform a self-diagnostics check
• Replace the drive if the fault continues to occur