12 specifications, Specifications – Yaskawa SI-EN3 Installation User Manual
Page 52
52
YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
12 Specifications
12
Specifications
◆
Specifications
Table 13 Option Specifications
Item
Specification
Model
SI-EN3
Supported Messages
• Explicit: Explicit Class 3, Unconnected
• I/O: Class 1, Listen Only, Input Only
I/O Assembly Instance
• Input: 7 types (4 to 44 Bytes)
• Output: 7 types (4 to 44 Bytes)
SI-EN3 Specification
Conformance Level A6: Passed
SI-EN3 Profile
AC Drive
Connector Type
RJ45 8-pin Straight Connector STP Cat 5e cable
Physical Layer Type
• Isolated Physical Layer
• TCP Protocol Transformer Isolated
IP Address Setting
Programmable from drive keypad or network
Communication Speed
Programmable from drive keypad or network:
10/100 Mbps, auto-negotiate
Number of Connections
• I/O: 2
• Explicit: 6
Duplex Mode
Half-forced, Auto-negotiate, Full-forced
Address Startup Mode
Static, BOOTP, DHCP
Ambient Temperature
-10
°C to +50°C (14°F to 122°F)
Humidity
95% RH or lower with no condensation
Storage Temperature
-20
°C to +60°C (-4°F to 140°F) allowed for short-term transport of the product
Area of Use
Indoor (free of corrosive gas, airborne particles, etc.)
Altitude
1000 m (3280 ft.) or lower
EtherNet_IM_E_conditional.fm 52 ページ 2012年10月31日 水曜日 午後12時53分