11 Troubleshooting
48
YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
■
Minor Faults and Alarms
LED Operator Display
Fault Name
oFC00
Option Fault (CN5-C)
Non-compatible option is connected.
Cause
Possible Solution
Non-compatible option
connected to the drive.
Connect the correct option to CN5-A.
LED Operator Display
Fault Name
oFC02
Option Fault
Option Flash write mode.
Cause
Possible Solution
Options AI-A3 or DI-A3 are
connected to the CN5-B port
while an option connected to
CN5-A.
• Only one type of AI-A3, DI-A3 or SI- option can be connected to the drive.
• The SI-EN3 option can only be connected to CN5-A
LED Operator Display
Minor Fault Name
CALL
Serial communication transmission error
Communication is not established.
Cause
Possible Solution
Minor Fault
(H2- = 10)
Communication wiring is
faulty, there is a short circuit,
or improper connection.
Check for wiring errors:
• Correct the wiring
• Remove ground shorts and reconnect loose wires
YES
Programming error on the
master side.
Check communications at start-up and correct programming errors.
Communication circuitry is
damaged.
• Perform a self-diagnostics check
• Replace the drive if the fault continues to occur
EtherNet_IM_E_conditional.fm 48 ページ 2012年10月31日 水曜日 午後12時53分