11 Troubleshooting
11
Troubleshooting
◆
Drive-Side Error Codes
Drive-side error codes appear on the drive digital operator. Causes of the errors and
corrective actions are listed in
. For additional error codes that may appear on the
drive digital operator, refer to the drive Technical Manual.
■
Faults
Both bUS (option communication error) and EF0 (External fault input from the option) can
appear as an alarm or as a fault. When a fault occurs, the digital operator ALM LED remains
lit. When an alarm occurs, the ALM LED flashes.
If communication stops while the drive is running, use the following questions as a guide to
help remedy the fault:
• Is the option properly installed?
• Is the communication line properly connected to the option? Is it loose?
• Is the controller program working? Has the controller/PLC CPU stopped?
• Did a momentary power loss interrupt communications?
Table 10 Fault Displays, Causes, and Possible Solutions
LED Operator Display
Fault Name
bUS
Option Communication Error
• After establishing initial communication, the connection was lost
• Only detected when the run command or frequency reference is assigned to the
option (b1-01 = 3 or b1-02 = 3)
Cause
Possible Solution
Master controller (PLC) has
stopped communicating
• Check that power is supplied to the PLC
• Check that PLC is not in program mode
Communication cable is not
connected properly
• Check for faulty wiring
• Correct any wiring problems
A data error occurred due to
noise
• Inspect items that can minimize the effects of electrical noise
• Counteract noise in the control circuit, main circuit, and ground wiring
• If a magnetic contactor is identified as a source of noise, install a surge absorber to
the contactor coil
• Make sure the cable used meets the EtherNet/IP requirements
• Make sure the option ground wire is connected between option FE terminal and the
drive ground terminal connected to earth ground
Option is damaged
If there are no problems with the wiring and the error continues to occur, replace the
option.
Connection Time-out
• The option Requested Packet Interval (RPI) timer timed out
• Make sure that RPI time is set properly
EtherNet_IM_E_conditional.fm 45 ページ 2012年11月5日 月曜日 午前11時39分