37

8 Output Assemblies (Drive Consumes)

8

Output Assemblies (Drive Consumes)

Note: The convention in this manual is from the PLC perspective. As such, an assembly is called an

“Output Assembly” when outputted from the PLC and received by this node. This section details

“Output Assemblies” that are “Consumed” by this drive.

Basic Speed Control Output - 20 (0x14)

Output

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

20

0

Fault

Reset

Run

Fwd

1

2

Speed Reference (Low Byte)

3

Speed Reference (High Byte)

Name

Description

Run Fwd

Forward Run Command
0: Stop
1: Forward Run

Fault Reset

Fault Reset
(0 to 1 transition: Fault Reset)

Speed Reference

Speed Command
Sets drive speed reference.
Speed reference data:
Frequency reference/2

SS

(SS: Speed scale)

Setting range: 0 to 0xFFFF
Example: setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/2

2

= 1024 = 0x0400 Hex or 10.24 Hz

Unit depends on o1-03.

EtherNet_IM_E_conditional.fm 37 ページ 2012年10月31日 水曜日 午後12時53分