Option led display – Yaskawa 1000 Series Drive Option - Profibus-DP Technical Manual User Manual
Page 9

4 Option Components
YASKAWA ELECTRIC
SIEP C730600 42B 1000-Series Option SI-P3 Technical Manual
9
Option LED Display
The option has four bicolor, red/green LEDs to relay information about power, communication status, and errors. The
operational states of the LEDs after completion of the power-up diagnostic process are described in
. Wait at least
2 seconds for the power-up diagnostic process to complete before verifying the states of the LEDs.
Table 4 Option LED States
Table 5 LED Operation After Power-up Diagnostic
{: On / : Flashing /
×: Off
LED
Display
Operating Status
Remarks
Color
Status
RUN
(Power)
Green
ON
Power supply ON
Power is supplied to the option, and the option hardware self-diagnostics check
is complete.
OFF
Power supply OFF
• The drive has no power supply.
• Option and drive are not connected properly and/or no power is supplied to
the option.
• An internal, self-diagnostic error occurred in the option.
ERR
(Option Error)
Red
ON
Option error
Self-diagnostic error occurred in the option.
Flashing
Drive connection
error
Connection error between option and drive. This includes node address setting
errors to parameter F6-30 on the drive side.
OFF
Normal operation
Drive and option are properly connected.
COMM
(Communication
Status)
Green
ON
Communication
connected
Normal send/receive between the option and the PROFIBUS-DP master.
OFF
No data exchange
There is a problem establishing communication between the option and the
PROFIBUS-DP master.
BF
(PROFIBUS-DP
Error)
Red
ON
Waiting for
communication
procedure setting
Communication-related parameters are in the process of being set or initialized
by the PROFIBUS-DP master.
Flashing
Communication
setting error
Communication parameter error from PROFIBUS-DP master.
OFF
Normal operation
LED shuts off when the PROFIBUS-DP master is finished setting
communication-related parameters.
LED
Communication
Status
Possible Cause
Solution
RUN ERR COMM BF
×
×
×
× No power
Drive has no power.
Check all wiring to the drive, then turn on the power.
Option is not properly connected to the
drive or is not receiving enough power.
Shut off the drive and make sure the option is
connected properly. Turn the power back on.
{
×
×
×
• Checking
connection with
the drive
• Waiting for data
from the master
• Option is reading the node address or
parameter configuration.
• Waiting for initial input data from
master device.
–
×
{
×
×
Option self-
diagnostics error
The option is damaged.
Cycle power to the drive. If the LED status does not
change, replace the option.
×
×
×
Problem connecting
to the drive
• Problem initializing the drive and the
option.
• Incorrect node address.
• Cycle power to the drive. If the LED status does
not change, replace the option.
• Check the node address setting in the drive (F6-10)
{
×
×
{
Waiting for data
from the master
device
Waiting for data from the master device.
(Set_Parm_Message or
Chk_Cfg_Message)
• Check master network settings.
• Make sure the master device is operating normally.
• Check terminal resistance settings on the data line.
• Check for problems with the data line and
connector.
• Check if the data line is connected properly to
communication connector CN5.
{
×
×
Incorrect data or
option time out
waiting for data
The communication settings in the
master are set incorrectly.
Check the communication settings in the master.
{
×
{
×
Sending or
receiving data
–
–