Communication cable specifications, Gsd files, Cable requirements – Yaskawa 1000 Series Drive Option - Profibus-DP Technical Manual User Manual
Page 17: Cable length

5 Installation Procedure
YASKAWA ELECTRIC
SIEP C730600 42B 1000-Series Option SI-P3 Technical Manual
17
Communication Cable Specifications
To ensure proper performance, Yaskawa recommends using PROFIBUS-DP-dedicated cables that fulfill the
specifications in
. Refer to the PROFIBUS-DP website at www.profibus.com for more information on cables.
Cable Requirements
Table 6 Communication Cable Requirements
Cable Length
Communication speed determines maximum permissible cable length.
shows the specifications for Type A bus
cables.
Table 7 Communication Cable Length
GSD Files
To facilitate network implementation, obtain a GSD file from one of the following websites depending on your region:
US: http://www.yaskawa.com
Europe: http://www.yaskawa.eu.com
Japan: http://e-mechatronics.com
Other areas: Contact your Yaskawa representative
Condition
Specifications
Impedance
135 to 165
Ω at a frequency of (3 to 20 MHz)
Capacity
30 pF/m maximum
Loop Resistance
110
Ω/km maximum
Core Cross-Section
0.34 mm
2
minimum
Core Diameter
0.64 mm minimum
Communication Speed (kbps)
Distance per Segment
9.6
1200 m (3937 ft.)
19.2
1200 m (3937 ft.)
45.45
1200 m (3937 ft.)
93.75
1200 m (3937 ft.)
187.5
1000 m (3280 ft.)
500
400 m (1312 ft.)
1500
200 m (656 ft.)
3000
100 m (328 ft.)
6000
100 m (328 ft.)
12000
100 m (328 ft.)