8 Parameter Process Data Object Formats
38
YASKAWA ELECTRIC SIEP C730600 42B 1000-Series Option SI-P3 Technical Manual
Note: When PNU is set to 0 and INDEX is set to MEMOBUS/Modbus register number, parameter values can be read and written
instead of using PNU number.
Note: MEMOBUS/Modbus register C1-01 is 200Hex
When PNU is 0 and INDEX is 200H(512 dec), C1-01 setting value can be read and written instead of using PNU 31 (dec) and
INDEX 01.
Example: Writing to C1-01
Command setting
Response
Example: Reading to d1-17
Command setting
Response
0
002AH MEMOBUS/Modbus #
42
0
002BH MEMOBUS/Modbus #
43
0
002CH MEMOBUS/Modbus #
44
0
002DH MEMOBUS/Modbus #
45
0
002EH MEMOBUS/Modbus #
46
0
002FH MEMOBUS/Modbus #
47
0
0030H MEMOBUS/Modbus #
48
0
0031H MEMOBUS/Modbus #
49
0
0032H MEMOBUS/Modbus #
50
0
0033H MEMOBUS/Modbus #
51
0
0034H MEMOBUS/Modbus #
52
0
xxx
xxx
0
00FFH MEMOBUS/Modbus #
255
Data type
Settings
Description
PKE
701FH
7: Change parameter value in array (word)
1FH = 31 (C1 parameter)
IND
1
C1-01
PWE
10
Assign 10
STW
–
up to Master command
HSW
–
up to Master command
Data type
Settings
Description
PKE
401FH
4: Transfer parameter value (array word)
1FH = 31 (C1 parameter)
IND
1
C1-01
PWE
0
N/A
STW
–
up to drive status
HSW
–
up to drive status
Data type
Settings
Description
PKE
6029H
6: Request parameter value from array
29H = 41 (d1 parameter)
IND
11H
11H = 17 (d1-17)
PWE
0
N/A
STW
–
up to Master command
HSW
–
up to Master command
Data type
Settings
Description
PKE
4029H
4: Transfer parameter value (array word)
29H = 41 (d1 parameter)
IND
11H
d1-17
PWE
258H
d1-17 value
DPV0 PNU
Number
Description
INDEX