Example: to read current ppo-write – Yaskawa 1000 Series Drive Option - Profibus-DP Technical Manual User Manual
Page 34

8 Parameter Process Data Object Formats
34
YASKAWA ELECTRIC SIEP C730600 42B 1000-Series Option SI-P3 Technical Manual
Response
Example: To read the data Type 1 PPO-Write 1st word
Command setting
Response
Example: To read current PPO-Write
Command setting
Response
PWE
0
N/A
STW
–
up to Master command
HSW
–
up to Master command
Data type
Settings
Description
PKE
438BH
4: Transfer parameter value (array word)
38BH=907 dec (PNU 907)
IND
5
5th Word data of PPO type 1
PWE
(ZSW)
ZSW data
ZSW
–
up to drive status
HIW
–
up to drive status
Data type
Settings
Description
PKE
6384H
6: Request parameter value from array
384H=900 dec (PNU 900)
IND
1
First Word data of PPO type 1
PWE
0
N/A
STW
–
up to Master command
HSW
–
up to Master command
Data type
Settings
Description
PKE
4384H
4: Transfer parameter value (array word)
384H=900 dec (PNU 900)
IND
1
First Word data of PPO type 1
PWE
6384H
PPO-Write 1st Word data
ZSW
–
up to drive status
HIW
–
up to drive status
Data type
Settings
Description
PKE
1388H
1: Request parameter value
388H=904 dec (PNU 904)
IND
0
Not array type
PWE
0
N/A
STW
–
up to Master command
HSW
–
up to Master command
Data type
Settings
Description
PKE
1388H
1: Transfer parameter value (word)
388H=904 dec (PNU 904)
IND
0
Not array type
PWE
1
1: Type 1 PPO-Write
2: Type 2 PPO-Write
3: Type 3 PPO-Write
4: Type 4 PPO-Write
5: Type 5 PPO-Write
ZSW
–
up to drive status
HIW
–
up to drive status
Data type
Settings
Description