ALM_RD: 05H (Read Alarm and Warning)

Table 13 ALM_RD_MOD

The ALM_RD command is used to read the following information about the status of faults and alarms.

• Present fault and alarm status list
• Fault history (Alarms are not saved in the history.)
• Details of faults

In the following case, a warning is generated and the command is ignored.

• If ALM_RD_MOD is other than a set value: Data setting warning (A.94)

The fault history is saved in EEPROM and is kept even when the control power is interrupted.

• If ALM_RD_MOD is set to 0: Fault code (1 byte) is entered to byte 6 of ALM_DATA, and byte 7 becomes the value

of the previous fault.

• If ALM_RD_MOD is set to 1: Fault code is entered in order of detection from ALM_DATA byte 6 so that byte 6 is

the most recent fault.

• When ALM_RD_MOD is set to 2: Fault code detected by the value set by the Alarm Index +1 is entered to bytes 7

and 8.

During normal operation (i.e., when no fault has occurred), the value is 00H.

Table 14 ALM_DATA

Byte

Command

Response

1

ALM_RD

ALM_RD

2

0

ALARM

3, 4

STATUS

5

ALM_RD_MOD

ALM_RD_MOD

6 to 15

0

ALM_DATA

16

WDT

RWDT

Byte

ALM_RD_MOD = 0

ALM_RD_MOD = 1

ALM_RD_MOD = 2

5

00H

01H

02H

6

U2-01

U3-01

Alarm Index

7

U2-02

U3-02

Lower byte of U3-(Alarm Index

+ 1)

8

U3-03

Upper byte of U3-(Alarm Index

+ 1)

9

U3-04

10

U3-05

11

U3-06

12

U3-07

13

U3-08

14

U3-09

15

U3-10

ALM_RD_MOD

ALM_DATA

Max.

Processing

Time

Parameter No.

0

Present fault (byte 6), past fault (byte 7)

0.1 s

U2-01 and U2-02

1

Fault history trace 10 max. (byte 6 to 15)

0.1 s

U3-01 to U3-10

2

Fault history (Alarms are not retained in the history.) (bytes 7 and 8)

0.1 s

U3-01 to U3-10