Alm_rd: 05h (read alarm and warning) – Yaskawa 1000 Series Drive Option - MECHATROLINK-II Technical Manual User Manual
Page 21

8 MECHATROLINK-II Commands
YASKAWA ELECTRIC
SIEP C730600 50A YASKAWA AC Drive-Option Card MECHATROLINK-II Technical Manual
21
ALM_RD: 05H (Read Alarm and Warning)
Table 13 ALM_RD_MOD
The ALM_RD command is used to read the following information about the status of faults and alarms.
• Present fault and alarm status list
• Fault history (Alarms are not saved in the history.)
• Details of faults
In the following case, a warning is generated and the command is ignored.
• If ALM_RD_MOD is other than a set value: Data setting warning (A.94)
The fault history is saved in EEPROM and is kept even when the control power is interrupted.
• If ALM_RD_MOD is set to 0: Fault code (1 byte) is entered to byte 6 of ALM_DATA, and byte 7 becomes the value
of the previous fault.
• If ALM_RD_MOD is set to 1: Fault code is entered in order of detection from ALM_DATA byte 6 so that byte 6 is
the most recent fault.
• When ALM_RD_MOD is set to 2: Fault code detected by the value set by the Alarm Index +1 is entered to bytes 7
and 8.
During normal operation (i.e., when no fault has occurred), the value is 00H.
Table 14 ALM_DATA
Byte
Command
Response
1
ALM_RD
ALM_RD
2
0
ALARM
3, 4
STATUS
5
ALM_RD_MOD
ALM_RD_MOD
6 to 15
0
ALM_DATA
16
WDT
RWDT
Byte
ALM_RD_MOD = 0
ALM_RD_MOD = 1
ALM_RD_MOD = 2
5
00H
01H
02H
6
U2-01
U3-01
Alarm Index
7
U2-02
U3-02
Lower byte of U3-(Alarm Index
+ 1)
8
U3-03
Upper byte of U3-(Alarm Index
+ 1)
9
U3-04
10
U3-05
11
U3-06
12
U3-07
13
U3-08
14
U3-09
15
U3-10
ALM_RD_MOD
ALM_DATA
Max.
Processing
Time
Parameter No.
0
Present fault (byte 6), past fault (byte 7)
0.1 s
U2-01 and U2-02
1
Fault history trace 10 max. (byte 6 to 15)
0.1 s
U3-01 to U3-10
2
Fault history (Alarms are not retained in the history.) (bytes 7 and 8)
0.1 s
U3-01 to U3-10