2 general data, 3 protective devices, General data – SMA WB 5000A-11 Installation User Manual
Page 80: Protective devices, 2 general data 11.3 protective devices

Technical Data
SMA Solar Technology AG
80
WB5A_6A-IA-IEN114540
Installation Manual
11.2 General Data
11.3 Protective devices
Width x height x depth
468 mm x 613 mm x 242 mm
Weight
62 kg
Length x width x height of packaging
396 mm x 803 mm x 596 mm
Transport weight
68 kg
Climatic category according to IEC 60721-2-1
4K4H
Operating temperature range
− 25°C … +60°C
Max. permissible value for relative humidity,
non-condensing
100%
Maximum operating altitude above mean sea
level
2 000 m
Noise emission (typical)
≤ 31 dB(A)
Power loss in night operation
0.25 W
Topology
LF transformer
Cooling concept
OptiCool
Fan connection
designed for safe disconnection in accordance with
DIN EN 50178:1998-04
Degree of protection for electronics according to
IEC 60529
IP65
Protection class (according to IEC 62103)
I
DC reverse polarity protection
Short-circuit diode
DC overvoltage protection
Thermally monitored varistors
AC short-circuit current capability
Current control
Grid monitoring
SMA Grid Guard 2.1
Maximum permissible fuse protection
40 A
Ground fault monitoring
Insulation monitoring: R
iso
> 0.7 M Ω
Galvanic isolation
available