beautypg.com

SMA WB 5000A-11 Installation User Manual

Page 25

background image

SMA Solar Technology AG

Electrical Connection

Installation Manual

WB5A_6A-IA-IEN114540

25

Load Disconnection Unit

You must install a separate miniature circuit-breaker for each inverter in order to ensure that the
inverter can be securely disconnected under load. The maximum permissible fuse protection can be
found in Section 11 "Technical Data" (page 76).
Detailed information and examples on the design of miniature circuit-breakers are available in the
Technical Information "Miniature circuit-breaker" to be found in the download area of
SMA Solar Technology AG at www.SMA.de/en.

DANGER!
Danger to life due to fire

In the event of parallel connection of more than one inverter to the same miniature
circuit-breaker, the protective function of the miniature circuit-breaker is no longer
guaranteed. It can result in a cable fire or destruction of the inverter.

• Never connect several inverters to the same miniature circuit-breaker.
• Observe the maximum permissible fuse protection of the inverter when selecting the

miniature circuit-breaker.

DANGER!
Danger to life through electric shock

When a generator (inverter) and a load are connected to the same miniature circuit-
breaker, the protective function of the miniature circuit-breaker is no longer guaranteed.
The currents from the inverter and the grid can accumulate to form overcurrents that are not
detected by the miniature circuit-breaker.

• Never connect the load between the

inverter and the miniature circuit-breaker
without protection.

• Always protect the load separately.

NOTICE!
Damage to the inverter due to the use of screw-type fuses as load disconnection
units
A screw-type fuse, e.g., DIAZED fuse or NEOZED fuse, is not a switch-disconnector and
must never be used as such. A screw-type fuse only acts as cable protection.
Disconnection under load using a screw-type fuse can damage the inverter.

• Use only a switch-disconnector or a miniature circuit-breaker as a load disconnection

unit.

This manual is related to the following products: