5.2 Connection to the Power Distribution Grid (AC)
5.2.1 Conditions for AC Connection
Cable Design
The maximum cable lengths relative to the cable cross-section are shown in the following table.
Cable Requirements
Connection requirements of the grid operator
Always observe the connection requirements of your grid operator.
Cable cross-section
Maximum cable length
WB 5000A/WB 5000A-11
WB 6000A/WB 6000A-11
6 mm²
18 m
15 m
10 mm²
31 m
25 m
16 mm²
49 m
41 m
Reducing line losses by half
If three inverters with symmetrical feed-in are combined to form a three-phase system, the
neutral conductor is not subjected to any load, and the line losses are halved. This
reduction of line losses by 50% increases the maximum cable length by 100%.
Object
Description
Value
A
External diameter
12 mm ... 25 mm
B
Cable cross-section
6 mm² ... 16 mm²
C
Stripping length
approx. 16 mm