4 sunny mini central operating parameters, Sunny mini central operating parameters – SMA SMC 5000 Installation User Manual
Page 40

Technical Documentation
SMA
Technologie AG
Page 40
SMC50_60-11:SE2006
Installation Guide
7.4 Sunny Mini Central Operating Parameters
The parameters with a grey background are only visible when in installer mode.
Any unauthorized modifications of the operating parameters can
• Result in serious injuries or casualties due to altered internal
safety precautions within the Sunny Mini Central
• Void the operating permission of the Sunny Mini Central
• Void the warranty of the Sunny Mini Central
Never change the operating parameters without explicit permis-
sion and instructions!
Name Unit
Range
Default
Betriebsart/
Operating Mode
MPP, UKonst, Stop,
Turbine, MPP
MPP
Default
GER/ENS
dFac-MAX
Hz/s
0.005 ... 4.0
0.25
dZac-MAX
mOhm
0 ... 20000
350
E_Total
kWh
0 ... 200000
Fac-Delta-
Hz
0 ... 4.5
0.19
Fac-Delta+
Hz
0 ... 4.5
0.19
Fan test
0
1
0
h_Total
h
0 ... 200000
Inst.-Code
NiTest/
testcurrent Zac
mA
0 ... 25000
16000
Riso
kOhm
0 ... 10000
1000
Speicherfunktion/
Memory Function
none
Speicher /
Storage
permanent / volatile
permanent
T-Max-Fan
°C
0 ... 100
90
T-Start
s
5 ... 1600
10 / 300
T-Start-Fan
°C
0 ... 100
70
T-Stop
s
1 ... 1800
2
T-Stop-Fan
°C
0 ... 100
50
Uac-Max / Vac-Max
V
180 ... 300
260
Uac-Min / Vac-Min
V
180 ... 300
198
Usoll-Konst/
Vconst-Setval
V
250 ... 600
600