Requirements for the Installation
Installation Guide
SMC50_60-11:SE2006
Page 21
Losses of the Sunny Mini Central 6000
The maximum cable lengths for the different cable cross-sections are as follows:
The Sunny Mini Central 5000/6000 is designed for 230 V grids. The voltage should
be within 198 V and 260 V and the frequency should be within 49.8 Hz and
50.2 Hz. All settings shown below are based on the German standard DIN VDE
0126. You are also able to use other settings.
The Sunny Mini Central 5000/6000 is equipped with an automatic 50 Hz / 60 Hz
utility frequency detection. It can therefore be connected to a 50 Hz or 60 Hz utility
without any further configuration changes. Pay attention to the local utility regula-
tions in any case.
Conductor cross-
section
4.0 mm²
6.0 mm²
10.0 mm²
16.0 mm²
Max. length
10 m
15 m
25 m
41 m
Limits for AC output
Voltage range
198 V ... 260 V
Frequency range
49.8 Hz ... 50.2 Hz
Voltage range
(without anti-islanding)
180 V ... 260 V
Frequency range
(without anti-islanding)
45.5 Hz ... 54.5 Hz
0,0%
0,2%
0,4%
0,6%
0,8%
1,0%
1,2%
1,4%
0 m
10 m
15 m
20 m
25 m
30 m
35 m
40 m
45 m
50 m
5 m
4,0 mm²
6,0 mm²
10,0 mm²
16,0 mm²
Sunny Mini Central 6000
Do not use cables where losses will exceed 1.0 %
Length
Lo
sse
s