Requirements for the Installation

Installation Guide

SMC50_60-11:SE2006

Page 21

Losses of the Sunny Mini Central 6000

The maximum cable lengths for the different cable cross-sections are as follows:

The Sunny Mini Central 5000/6000 is designed for 230 V grids. The voltage should
be within 198 V and 260 V and the frequency should be within 49.8 Hz and
50.2 Hz. All settings shown below are based on the German standard DIN VDE
0126. You are also able to use other settings.

The Sunny Mini Central 5000/6000 is equipped with an automatic 50 Hz / 60 Hz
utility frequency detection. It can therefore be connected to a 50 Hz or 60 Hz utility
without any further configuration changes. Pay attention to the local utility regula-
tions in any case.

Conductor cross-

section

4.0 mm²

6.0 mm²

10.0 mm²

16.0 mm²

Max. length

10 m

15 m

25 m

41 m

Limits for AC output

Voltage range

198 V ... 260 V

Frequency range

49.8 Hz ... 50.2 Hz

Voltage range

(without anti-islanding)

180 V ... 260 V

Frequency range

(without anti-islanding)

45.5 Hz ... 54.5 Hz

0,0%

0,2%

0,4%

0,6%

0,8%

1,0%

1,2%

1,4%

0 m

10 m

15 m

20 m

25 m

30 m

35 m

40 m

45 m

50 m

5 m

4,0 mm²

6,0 mm²

10,0 mm²

16,0 mm²

Sunny Mini Central 6000

Do not use cables where losses will exceed 1.0 %

Length

Lo

sse

s