Requirements for the Installation

Installation Guide

SMC50_60-11:SE2006

Page 23

The indicated power on the x axis complies approx. 6.2 kW per phase.

In consequence you should install only one Sunny Mini Central 5000/6000 per
phase. To install a plant with a higher power that does not stop feeding because of
AC over voltage, you should check the connection conditions of the Sunny Mini Cen-
tral 5000/6000 (e. g. by using a cable with a higher cross-section).

Example

The grid voltage without feeding averages 230 V.

The grid impedance at the connection point averages 1.2 Ohm.

Grid Impedance [Ohm]

Power [kW] per Phase

0

5

10

15

20

25

30

0,5

0,6

0,7

0,8

0,9

1,0

1,1

1,2

1,3

1,4

1,5

230 V