Connection of AC output

Please follow the steps below:

1.

Check the grid voltage. If it is above 260 V
(German standard), the Sunny Mini Central
5000/6000 stops operation. The local public
utility company should solve this problem.

max. 260 V!

The maximum grid voltage for feeding

operation is 260 V!

2.

Disconnect the grid (switch off the circuit break-
er), secure it against accidental reactivation and
ensure that it is disconnected.

Before opening the Sunny Mini Central

5000/6000 check whether the AC

output is safely isolated from supply!

3.

Unscrew the lid from the enclosure of the Sunny
Mini Central 5000/6000 and remove the lid.

4.

Connect the AC cable as illustrated in the figure
on the side. Use the cable gland that is included
in the delivery of your Sunny Mini Central
5000/6000. Phase (L) and Neutral (N) may not
be mixed up.

Connection of „L“ and „N“

1.

2.

3.

Off!

Betrieb

Operatio

n

Erdschlu

ss

Earth Fa

ult

Photovoltaik-W

echselrichter

Photovoltaic inver

ter

Störung

Failure

N

L1

230 Vac:

L

N